LG AMNH076LQL0 Service Manual page 189

Multi type air conditioner
Hide thumbs Also See for AMNH076LQL0:
Table of Contents

Advertisement

12) Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65
Display
Title
code
D-pipe sensor (Inverter)
41
Air sensor
44
Condenser Pipe sensor
45
Suction Pipe sensor
46
D-pipe sensor (Constant)
47
Heat sink sensor
65
Cause of error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 kΩ or ∞, then sensor is abnormal.
If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal.
Troubleshooting Guide
Check point & Normal condition
• Normal resistor : 200KΩ / at 25°C (Unplugged)
• Normal voltage : 4.5Vdc / at 25°C (plugged)
• Normal resistor : 10KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
• Normal resistor : 5KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
• Normal resistor : 5KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
• Normal resistor : 200KΩ / at 25°C (Unplugged)
• Normal voltage : 4.5Vdc / at 25°C (plugged)
• Normal resistor : 10KΩ / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)