Troubleshooting Guide
7) Troubleshooting CH23
Display
Title
code
DC Link Low voltage
23
Check Point
1. Check the Tab1 connection condition. (Refer to outdoor wiring diagram)
2. Check the CN_COIL(IN), CN_COIL(OUT) connection condition.
3. Check the DC Link voltage at not operating(260V )
4. Check the DC Link voltage at Comp operating(500V )
190 Multi type Air Conditioner
Cause of error
• DC Link volt is below
300V
Check point & Normal condition
• Check point & Normal condition
• Check the TAB1 is connect.
• At not operating : DC Link voltage(260V )
• At Comp operating : DC Link voltage(500V )