6

DATA

6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
Service Ref.
PUHZ-SW75VHA(-BS).UK
PUHZ-SW75VHAR3(-BS).UK
PUHZ-SW75VHAR4(-BS).UK
PUHZ-SW100VHA(-BS).UK
PUHZ-SW100VHAR3(-BS).UK
PUHZ-SW100YHA(-BS).UK
PUHZ-SW100YHAR1(-BS).UK
PUHZ-SW100YHAR3(-BS).UK
PUHZ-SW100V/YHAR4(-BS).UK
PUHZ-SW120VHA(-BS).UK
PUHZ-SW120VHAR3(-BS).UK
PUHZ-SW120YHA(-BS).UK
PUHZ-SW120YHAR1(-BS).UK
PUHZ-SW120YHAR3(-BS).UK
PUHZ-SW120V/YHAR4(-BS).UK
6-2. COMPRESSOR TECHNICAL DATA
PUHZ-SW75VHAR3.UK
PUHZ-SW75VHA-BS.UK
PUHZ-SW75VHAR3-BS.UK
Service Ref.
Compressor model
U-V
Winding
U-W
Resistance
( " )
W-V
PUHZ-SW120VHAR3.UK
PUHZ-SW120VHAR4.UK
PUHZ-SW120VHA-BS.UK
PUHZ-SW120VHAR3-BS.UK
Service Ref.
PUHZ-SW120VHAR4-BS.UK
Compressor model
U-V
Winding
U-W
Resistance
( " )
W-V
OCH533D
10 m
20 m
3.2
3.6
3.2
3.35
4.6
4.8
4.6
4.8
4.6
4.8
4.6
4.8
Additional charge is required for pipes
longer than 10 m.
PUHZ-SW75VHA.UK
TNB220FLHMT
0.88
0.88
0.88
PUHZ-SW120VHA.UK
ANB42FNEMT
0.19
0.19
0.19
Piping length (one way)
30 m
40 m
50 m
4.0
4.6
3.5
4.1
5.0
5.6
6.2
5.0
5.6
6.2
5.0
5.6
6.2
5.0
5.6
6.2
PUHZ-SW75VHAR4.UK
PUHZ-SW75VHAR4-BS.UK
SNB220FAGMC-L1
0.95
0.95
0.95
PUHZ-SW100YHA.UK
PUHZ-SW100YHAR1.UK
PUHZ-SW100YHAR3.UK
PUHZ-SW100YHAR4.UK
PUHZ-SW100YHA-BS.UK
PUHZ-SW100YHAR1-BS.UK
PUHZ-SW100YHAR3-BS.UK
PUHZ-SW100YHAR4-BS.UK
ANB33FNDMT
0.30
0.30
0.30
13
Initial
60 m
75 m
charged
3.2
3.2
6.8
7.4
4.6
6.8
7.5
4.6
6.8
7.4
4.6
6.8
7.5
4.6
(at 20°C)
PUHZ-SW100VHA.UK
PUHZ-SW100VHAR3.UK
PUHZ-SW100VHAR4.UK
PUHZ-SW100VHA-BS.UK
PUHZ-SW100VHAR3-BS.UK
PUHZ-SW100VHAR4-BS.UK
ANB33FNEMT
0.19
0.19
0.19
(at 20°C)
PUHZ-SW120YHA.UK
PUHZ-SW120YHAR1.UK
PUHZ-SW120YHAR3.UK
PUHZ-SW120YHAR4.UK
PUHZ-SW120YHA-BS.UK
PUHZ-SW120YHAR1-BS.UK
PUHZ-SW120YHAR3-BS.UK
PUHZ-SW120YHAR4-BS.UK
ANB42FNDMT
0.30
0.30
0.30

Hide quick links: