Installation checklist and start-up

Installation checklist

Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person. Read the
instructions
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. See
conditions.
The unit is fixed properly to floor. See
The cooling air will flow freely.
ELECTRICAL INSTALLATION See
The motor and the driven equipment are ready for start.
The EMC filter (option +E202) is disconnected if the drive is connected to an IT (ungrounded) system.
The drive is grounded properly:
1) adequately sized PE conductor
2) properly tightened PE conductor.
The supply (input power) voltage matches the nominal input voltage of the drive.
The supply (input power) connection to the input terminals are OK and the phase order is correct.
Appropriate supply (input power) fuses are installed.
The motor connections at the output terminals are OK.
The motor cable is routed away from other cables.
Settings of the auxiliary voltage transformer of the drive.
Settings of the internal transformer in the DSU.
There are no power factor compensation capacitors in the motor cable.
The external control connections of the drive are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Supply (input power) voltage cannot be applied to the output of the drive (with a bypass connection).
For drives with Category 1 Emergency stop function (option +Q952 or +Q964): The time relay has been set to a
suitable value (somewhat longer than the stop ramp of the inverter units).
All shrouds are in place.
on the first pages of this manual before you work on the unit.
Electrical installation,
Mechanical installation.
Planning the electrical installation, Electrical installation.