Electromagnetic Radiation
Do not install the inverter near sources of electromagnetic radiation.
Atmospheric Pollution
Do not install the inverter in an environment, which contains atmospheric pollutants
such as dust, corrosive gases, etc.
Water
Take care to site the inverter away from potential water hazards, e.g. do not install
the inverter beneath pipes that are subject to condensation. Avoid installing the
inverter where excessive humidity and condensation may occur.
Installation and cooling
CAUTION
The inverters MUST NOT be mounted horizontally.
The inverters can be mounted without any clearance at either side.
When mounting inverters one above the other, the specified environmental
conditions must not be exceeded.
Independent of this, these minimum distances must be observed.
Frame Size C
Frame Size D, E
Frame Size F
Frame Size FX, GX above 250 mm
No equipment that could have a negative effect on the flow of cooling air should be
installed in this area. Make sure that the cooling vents in the inverter are positioned
correctly to allow free movement of air.
MICROMASTER 430
Operating Instructions
6SE6400-5AE00-0BP0
above and below 100 mm
above and below 300 mm
above and below 350 mm
below 150 mm
in front 40 mm (FX), 50 mm (GX)