Troubleshooting - Samsung AC024JXADCH Installation Manual

Hide thumbs Also See for AC024JXADCH:
Table of Contents

Advertisement

Troubleshooting

The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized
Service Center.
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
No.
Error Code
1
E108
Error due to repeated communication address
2
E121
Error on room temperature sensor of indoor unit (Short or Open) Indoor unit Room Thermistor Open/Short
3
E122
Error on EVA IN sensor of indoor unit (Short or Open)
4
E123
Error on EVA OUT sensor of indoor unit (Short or Open)
5
E153
Error on float switch (2nd detection)
6
E154
Indoor fan error
7
E198
Error on thermal fuse of indoor unit (Open)
Communication error between indoor unit and outdoor unit
(Pre tracking failure or when actual number of indoor units
are different from the indoor unit quantity setting on the
8
E201
outdoor unit) Error due to communication traking failure
after initial power is supplied. (The error occurs regardless of
the number of units.)
Communication error between indoor unit and outdoor unit
9
E202
(When there is no response from indoor units after tracking
is completed)
"Communication error between outdoor unit inv - main micom
10
E203
(For PF #4~#6 controller, error will be determined from the time
when compressor is turned on)"
11
E221
Error on outdoor temperature sensor (Short or Open)
12
E231
Error on outdoor COND OUT sensor (Short or Open)
Error on discharge temperature sensor of compressor 1 (Short
13
E251
or Open)
14
E320
Error on OLP sensor (Short or Open)
15
E403
Compressor down due to freeze protection control
16
E404
System stop due to overload protection control
17
E416
System stop due to discharge temperature
18
E422
Blockage detected on high pressure pipe
38
Meaning
Remarks
Check on repeated indoor unit main address
Indoor unit EVA_IN Thermistor Open/Short
Indoor unit EVA_OUT Thermistor Open/
Short
"Indoor unit Float Switch Open/Short
Drain Pump operation Check"
Check on indoor unit indoor Fan operation
Thermal Fuse Open Check of indoor unit
Terminal Block
Check indoor quantity setting in outdoor
Check electrical connection and setting
between indoor unit and outdoor unit
Check electrical connection and setting
between indoor unit MAIN PBA - INVERTER PBA
Check Outdoor sensor Open / Short
Check Cond-Out sensor Open / Short
Check Discharge sensor Open / Short
Check OLP sensor Open / Short
Check Outdoor Cond.
Check Comp. when it start
-
1. Check if the service valve is open
2. Check for refrigerant leakage(pipe con-
nections, heat exchanger) and charge
refrigerant if necessary
3. Check if there's any blockage on refriger-
ant cycle(indoor unit/outdoor unit)
4. Check if additional refrigerant has been
added after pipe extension