Local Parameter Setting - YOKOGAWA EJX110A Installation Manual

Ejx series and eja-e series differential pressure and pressure transmitters
Hide thumbs Also See for EJX110A:
Table of Contents

Advertisement

The zero-adjustment screw is located inside the cover.
Use a slotted screwdriver to turn the zero-adjustment
screw. Equalize the transmitter, then turn the screw
clockwise to increase the output or counterclockwise to
decrease the output. The zero point adjustment can be
made with a resolution of 0.01% of the setting range. The
degree of zero adjustments varies with the screw turning
speed; turn the screw slowly to make a fine adjustment,
quickly to make a rough adjustment.
When using differential pressure transmitters for level
measurement and if you cannot obtain the lower range
value from the actual measurement value of 0%, refer to
subsection 6.2.2(2).
6.2.2 Adjusting Zero Point for Gauge/
Absolute Pressure Transmitters
(1) When you can obtain the Low Range Value
from the actual measured value of 0%
(0 kPa, atmospheric pressure);
For pressure measurement using gauge pressure
transmitters, follow the steps below before performing
zero point adjustment.
1) Close the tap valve (main valve).
2) Loosen the fill plug so that the pressure applied to the
transmitter is only the head of the seal liquid.
3) Adjust the zero point at this status.
4) After the adjustment, close the fill plug and then
gradually open the tap valve.
Use a slotted screwdriver to turn the zero-adjustment
screw. Turn the screw clockwise to increase the output or
counterclockwise to decrease the output. The zero point
adjustment can be made with a resolution of 0.01% of the
setting range. Since the degree of the zero adjustment
varies with the screw turning speed, turn the screw slowly
to make a fine adjustment and quickly to make a rough
adjustment.
(2) When you cannot obtain the Low Range
Value from the actual measured value of
0%;
Adjust the transmitter output to the actual measured
value obtained by a digital manometer or a glass gauge.
[Example]
The measuring range of 50 to 250 kPa; the actual
measured value of 130 kPa.
Actual measured value=
Turn the screw to match the output signal to the actual
measured value.
130–50
x100=40.0%
250–50
(=10.4mA)
<6. Operation>
6.3

Local Parameter Setting

WARNING
The local push button on the integral indicator must
not be used in a hazardous area. When it is necessary
to use the push button, operate it in a non- hazardous
location.
IMPORTANT
• Do not turn off the power to the transmitter
immediately after performing parameter setting.
Powering off within 30 seconds of performing this
procedure will return the parameter to its previous
setting.
• The parameter of Ext SW must be"Enabled"
to perform this configuration. See the user's
manual IM 01C25T (HART/BRAIN) for the setting
procedure.
• The Local Parameter Setting function is available
with HART or BRAIN communication type.
6.3.1 Local Parameter Setting (LPS)
Overview
Parameter configuration by the external adjustment
screw and push button (integral indicator code E) offers
easy and quick setup for parameters of Tag number, Unit,
LRV, URV, Damping,Output mode (linear/square root),
Display out 1, and Re-range by applying actual pressure
(LRV/URV). There is no effect on measurement signal
(analog output or communication signal) when Local
Parameter Setting is carried out.
External adjustment screw cover
Figure 6.3
External Adjustment Screw
Push-button
Figure 6.4
Range –Setting Switch (push button)
49
F0604.ai
Integral indicator
F0605.ai
IM 01C25A01-01E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents