Controller Stop Mode (Manual Adjustment Of Burner Load) - Baxi Power HT 1.280 Installation, Operation And Maintenance Manual

Condensing gas boiler
Hide thumbs Also See for Power HT 1.280:
Table of Contents

Advertisement

Installation
5.10 Controller Stop Mode
(Manual Adjustment of
Burner Load)
36
For setting and controlling the CO
the control stop function .
1.
Boiler temperature
Press operation mode button Heating Operation for approximately 3 seconds
=> the message Controller Stop Function ON is displayed.
2. Wait, until the display has reached the basic display again.
3.
Press information button
=> The message Controller stop setpoint adjust appears in the display. The actu-
al modulation degree will be displayed on the display.
4. Press OK button
= > The nominal value can now be changed.
5. Press OK button
=> The displayed nominal value is accepted by the control.
Note: The regulator stop function is stopped by pressing the operating mode but-
ton Heating Operation for approximately 3 seconds, reaching the maximum boiler
temperature or a time limit.
values the Power HT in operated in
2
> 3 s
358 436 08.10