Controller Stop Mode (Manual Adjustment Of Burner Load) - Baxi POWER HT-A 1.430 Installation Manual

Gas condensing boilers
Table of Contents

Advertisement

Installation
5.10 Controller Stop Mode
(Manual Adjustment of
Burner Load)
5
2
For setting and controlling the CO
function .
1.
xxxxxxxxxxxx
Press operation mode button Heating Operation for approximately 3 seconds
=> the message Controller Stop Function ON is displayed.
2. Wait, until the display has reached the basic display again.
3.
Press information button
=> The message Controller stop setpoint adjust appears in the display. The ac-
tual modulation degree will be displayed on the display.
4. Press OK button
= > The nominal value can now be changed.
5. Press OK button
=> The displayed nominal value is taken over by the control.
Note: The regulator stop function is stopped by pressing the operating mode but-
ton Heating Operation for approximately 3 seconds, reaching the maximum boiler
temperature or a time limit.
If a heat demand from a cylinder with internal indirect coil is present, this demand
will continue to be met while the controller stop function is running.
values the in operated in the
2
> 3 s
POWER HT-A
control stop