Fisher FSPI-180AE1 Service Manual page 51

Spilt air conditioner unit ceiling & floor type
Table of Contents

Advertisement

2.4.1.5. Indoor fan Speed has been out of control. (Only for the units used AC motor)
Shut off the power supply
and turn it on 5 seconds
later.Is it still displaying
the error code?
Yes
S h u t o f f t h e p o w e r
supply , rotate the cross
fan by hand. Does it
rotate properly?
Yes
Check the wires of
fan motor. Are all the
connections good?
Yes
Check the resistance value of
indoor fan motor, is it normal?
Yes
Replace indoor PCB.
2.4.1.7. Refrigerant Leakage Detection
Electrical Control System
No
The unit operates normally.
Disassembly the
connection between
No
fan and motor, check if
the bearing is normal?
No
Correct the connections.
No
Replace the bearing.
Yes
Replace indoor fan motor.
No
Troubleshooting
51