Fisher FSPI-180AE1 Service Manual page 43

Spilt air conditioner unit ceiling & floor type
Table of Contents

Advertisement

When cooling, the setting temperature rises 1℃ (be lower than 30℃) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1℃ (be higher than 17℃) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode but doesn't turns off,
but for console, the unit will turn off.
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes
when power returns.
1.3.9 Drain pump control (only optional )
1.3.10 Follow me (with wireless remote)
1)
If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote
controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the
indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not
respond. When the unit is running with follow-me function, the PCB will control the unit according to the
temperature from follow-me signal, and the temperature collection function of room temperature sensor
will be shielded.
2)
When the follow-me function is available, the PCB will not respond according to the setting temperature
from follow-me signal every 3 minutes.
3)
The PCB will take action to the mode change information from remote controller signal, and the
follow-me function will be turned off. (if the wired remote controller does not initiate follow me function).
4)
When the unit is running with follow-me function, if the PCB doesn't receive any signal from remote
controller for 7 minutes or pressing FOLLOW ME button again, the follow-me function will be turned off
automatically, and the temperature collection function of room temperature sensor will be available, the
PCB will control the unit according to the room temperature detected from its own room temperature
sensor and setting temperature.
5)
When the indoor PCB receives the follow-me signal from wired remote controller, the control is the
same as that from wireless remote controller, but buzzer will not respond. When the PCB receives
Electrical Control System
Electrical Control Function
43