General; Combustion, Dilution And Ventilation Air - Lennox EL296DFV Installation Instructions Manual

Elite series gas furnace downflow air discharge
Hide thumbs Also See for EL296DFV:
Table of Contents

Advertisement

• Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
• Air filters must be installed in the system and must be
maintained during construction.
• Air filters must be replaced upon construction comple­
tion.
• The input rate and temperature rise must be set per the
furnace rating plate.
• One hundred percent (100%) outdoor air must be pro­
vided for combustion air requirements during construc­
tion. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
• The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean-up.
• All furnace operating conditions (including ignition, in­
put rate, temperature rise and venting) must be verified
according to these installation instructions.

General

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­
lowing general recommendations must be considered
when installing a EL296DFV furnace:
• Place the furnace as close to the center of the air dis­
tribution system as possible. The furnace should also be
located close to the chimney or vent termination point.
• When the furnace is installed in non-direct vent applica­
tions, do not install the furnace where drafts might blow
directly into it. This could cause improper combustion
and unsafe operation.
• When the furnace is installed in non-direct vent applica­
tions, do not block the furnace combustion air opening
with clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
• When the furnace is installed in an attic or other insu­
lated space, keep insulation away from the furnace.
• When the furnace is installed in an unconditioned
space, consider provisions required to prevent freezing
of condensate drain system.
CAUTION
EL296DFV unit should not be installed in areas nor­
mally subject to freezing temperatures.
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
Combustion, Dilution & Ventilation Air
If the EL296DFV is installed as a Non-Direct Vent Fur­
nace, follow the guidelines in this section.
NOTE - In Non-Direct Vent installations, combustion air
is taken from indoors or ventilated attic or crawlspace
and flue gases are discharged out-doors.
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rust­
ing and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the com­
bustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today's homes, tight construction
practices make it necessary to bring in air from outside
for combustion. Take into account that exhaust fans, ap­
pliance vents, chimneys, and fireplaces force additional
air that could be used for combustion out of the house.
Unless outside air is brought into the house for combus­
tion, negative pressure (outside pressure is greater than
inside pressure) will build to the point that a downdraft
can occur in the furnace vent pipe or chimney. As a result,
combustion gases enter the living space creating a po­
tentially dangerous situation.
In the absence of local codes concerning air for combus-
tion and ventilation, use the guidelines and procedures in
this section to install EL296DFV furnaces to ensure effi­
cient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
pip-ing. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (ANSI-