Additional Venting Requirements - Carrier 58CTA Installation And Service Instructions Manual

2 stage deluxe induced-combustion 4-way multipoise furnace series 110
Table of Contents

Advertisement

Caution!! For the following applications, use the minimum vertical heights as specified below
For all other applications, follow exclusively the National Fuel Gas Code
FURNACE ORIENTATION
VENT ORIENTATION
Vent elbow left, then up
Downflow
Horizontal Left
Horizontal Left
Horizontal Left
Vent elbow up then left
Downflow
Vent elbow up, then right
Downflow
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
*4 in. inside casing or vent guard
**Including 4 in. vent section(s)
1. For common vent, vent connector sizing and vent material:
United States--use the NFGC
Canada--use the NSCNGPIC
2. Immediately increase to 5-inch or 6-inch vent connector outside furnace casing when 5-inch vent connector is required, refer to Note 1
above.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when
KGAVG0101DFG, Downflow Vent Guard Kit, is used in the downflow position.
4. Type-B vent where required, refer to Note 1 above.
5. Four-inch single-wall (26 ga. min.) vent must be used inside furnace casing and when the KGAVG0101DFG Downflow Vent Guard Kit
is used external to the furnace.
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with lower vent configuration.
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC or
KGACA02015FC, for sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, spaced approximately 180° apart.
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120° apart. Secure Type-B vent
connectors per vent connector manufacturer's recommendations.
10. The total height of the vent and connector shall be at least seven feet for the 154,000 Btuh gas input rate model when installed in a
downflow application with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig.
39.)

ADDITIONAL VENTING REQUIREMENTS

A 4" round vent elbow is supplied with the furnace. A 5-inch or 6-
inch vent connector may be required for some model furnaces. A
field-supplied 4-inch to 5-inch or 4-inch to 6-inch sheet metal
Fig. 46—Horizontal Right Application-Vent Elbow Left
FURNACE INPUT(BTU/HR)
154,000
132,000
Fig. 38
110,000(036/-12 only)
Vent elbow right,
154,000
then up
132,000
Fig. 41
Vent Elbow up
154,000
Fig. 42
132,000
Vent elbow right
154,000
Fig. 43
110,000
Fig. 36
(036/-12 only)
110,000
Fig. 39
(036/-12 only)
Venting Notes for Fig. 34-46
SEE NOTES: 1,2,4,5,7,8,9
MINIMUM
VENT DIAMETER (IN.)*
5
5
5
5
5
5
increaser fitting is required when 5-inch or 6-inch vent connector
is used. See Fig. 34-46 Venting Orientation for approved vent
configurations.
31
MINIMUM VERTICAL VENT HEIGHT (FT)**
12
7
7
7
10
10
A02068