Cycle Component Function Explanation - Samsung AM072FXVAFH series Service Manual

Am0724fxvafh
Table of Contents

Advertisement

7-21 Cycle Component Function Explanation

1. Accumulator : Separating the incoming liquid refrigerant to the compressor in order to prevent liquid refrigerant.
2. Oil Separator : Separating the oil from the refrigerant discharged from the compressor, and the separated oil is returned to the compressor.
3. Intercooler : Supercooled liquid refrigerant through the heat exchanger and makes the medium pressure gas refrigerant injected into the
compressor.
4. IPM Cooler : IPM (Intelligent Power Module) by cooling to prevent overheating.
5. High/Low Pressure Sensor : Measure high/low Pressure of system.
6. High Pressure Switch : Suspend immediately for protection of system if high pressure of system exceeds setting value.
7. Outdoor EEV (Main EEV) : Adjust the incoming refrigerant to the outdoor heat exchanger during heating operation.
8. ESC EEV: Securing of the super cooling degree by controling a refrigerant amount passing through subcooler.
9. 4Way Valve : Change the direction of flow of the refrigerant to the cooling / heating operation.
10. ARV (Accumulator Oil Return Valve) : Remaining at the bottom of the Accumulator recovered oil to the compressor.
11. MainCooling Valve : In the main cooling operation, sending the high pressure refrigerant to indoor unit in heating mode.
12. It opens at single cooling operation and is used as super heat temperature control at heating operation.
13. Hotgas Valve : Sending the high pressure gas to low pressure pipe in order to protect low pressure.
14. Hotgas Valve 2 : In the cooling operation, changing high pressure pipe to low pressure pipe.
15. EVI SOL V : This valve opens when using the vapor Injection.
16. EVI BYPASS V : This valve opens in the sub cooling control. It's closed when using the vapor injection.
17. Discharge Temperature Sensor : Measure the temperature of the refrigerant discharged from the compressor.
18. Suction Temperature Sensor : Measure the temperature of the refrigerant to the compressor suction.
19. Cond. Out Temperature Sensor : Measure the temperature of the outdoor heat exchanger of the air conditioning operation.
20. EVI In/Out Temperature Sensor : Measure the temperature of the refrigerant inlet and outlet of the Subcooler.
21. Liquid Pipe Temperature Sensor : Measure the temperature of supercooling refrigerant in the outdoor unit of the air conditioning.
22. Comp. Top Temperature Sensor : Measure the temperature of compressor top cover.
23. Ambient Temperature Sensor : Measure the outdoor temperature.
24. Water Temperature Sensor : Plate Heat Exchanger internal temperature measurement.
25. Control box temp. Sensor : Control box internal temperature measurement, thermal protection used for the control.
26. Receiver : Storing the refrigerant piping system, a stable liquid refrigerant supply.
27. Liquid Tube Valve : Refrigerant in the outdoor unit side, the indoor unit during heating operation to rotate the valve operation.
7-16
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents