4-4-57 Error due to using single type outdoor unit in a module installation
Outdoor Unit Display
-
Indoor Unit Display
Judgment Method
Special Cause
1. Cause of problem
Is outdoor unit single type exclusive
use model (non-modular model)?
Is the outdoor unit by module installed?
Outdoor unit single type exclusive use
model (non-modular model), can not be
module installation.
(single type only installation)
Samsung Electronics
Yes
Is the outdoor unit EEPROM accurately
connected to connector?
Yes
Download relevant model EEPROM and
then reset.
Execute automatic commissioning
for UP cancellation after EEPROM
download.
No
Yes
Troubleshooting
No
Connect outdoor unit EEPROM
and then reset.
4-117