Connecting-up
5.3 EMC-compliant installation
Diagrams for grounding and high-frequency equipotential bonding measures
The following diagram illustrates all grounding and high-frequency equipotential bonding
measures using the example of a cabinet with a SINAMICS G120.
Grounding measures
①
High-frequency equipotential bonding measures
②
③
④
⑤
Figure 5-9
56
Conventional grounding without any special HF properties
Electrically conductive connection to the mounting panel through the largest possible surface
HF equipotential bonding
Connect the shield through a large contact surface and ground
Connect the shield through an electrically conductive heavy-gauge threaded joint (gland) and
ground
Grounding and high-frequency equipotential bonding measures in the drive system and
in the plant
Hardware Installation Manual, 12/2015, A5E33294624B AD
Power Module PM240-2