Section 6
TROUBLESHOOTING FLOWCHARTS
Problem 2 - Generator Produces Zero Voltage or Residual Voltage (5-12 VAC)
(continued)
TEST 4 -
PERFORM FIXED
EXCITATION /
CHECK VOM FUSES -
E
REPLACE FUSES
G
ROTOR AMP
VERIFY AMP METER
- THEN RETEST
DRAW
FUNCTIONS
F
TEST 11 -
BAD
(PERFORM BOTH TEST 7 & 8)
CHECK ROTOR
ASSEMBLY
TEST 8 - CHECK
TEST 7 - TEST
REPAIR
EITHER OR
SENSING LEADS /
STATOR DPE
OR
REPAIR
BOTH BAD
POWER WINDINGS
WINDING
REPLACE
OR
REPLACE
GOOD
GOOD
INSULATION
INSULATION
RESISTANCE
RESISTANCE
BAD
BAD
TEST PAGE 11
TEST PAGE 11
Page 23