Neutral Voltage Menu; Nps Overvoltage Menu; Frequency Menu - Siemens 7SG11 Technical Manual

Argus 8
Hide thumbs Also See for 7SG11:
Table of Contents

Advertisement

5 Neutral Voltage Menu

SETTING
Gn 3Vo Element 1 Setting
sets the pick up level of NVD Element 1
Gn 3Vo Element 1 Delay
sets the DTL timer value for NVD Element 1
Gn 3Vo Element 2 Setting
Gn 3Vo Element 2 Delay

6 NPS Overvoltage Menu

SETTING
Gn V2 Element 1 Setting
sets the pick up level of NPS Element 1
Gn V2 Element 1 Delay
sets the DTL timer value for NPS Element 1
Gn V2 Element 2 Setting
Gn V2 Element 2 Delay

7 Frequency Menu

SETTING
Gn F Element 1 Operation
sets the mode of operation of Frequency Element 1,
whether under or over-frequency
Gn F Element 1 Setting
sets the pick up level for Frequency Element 1
Gn F Element 1 Delay
Sets the DTL timer value for Frequency Element 1
Gn F Element 1 Inhib
sets which voltage element operation should block
Frequency Element 1 from operating
Gn F Element 2 Operation
Gn F Element 2 Setting
Gn F Element 2 Delay
Gn F Element 2 Inhib
Gn F Element 3 Operation
Gn F Element 3 Setting
Gn F Element 3 Delay
Gn F Element 3 Inhib
Gn F Element 4 Operation
Gn F Element 4 Setting
Gn F Element 4 Delay
Gn F Element 4 Inhib
©2011 Siemens Protection Devices Limited
7SG11 Argus 8 Relay Settings
RANGE
0FF, 1 – 100V step 0.5V
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
As per Element 1
As per Element 1
RANGE
0FF, 1 – 100V step 0.5V
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
As per Element 1
As per Element 1
RANGE
OFF, O/F, U/F
47.00Hz – 62.00Hz step 0.01Hz
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
VE1, VE2, VE3, VE4
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
As per Element 1
Chapter 3 Page 6 of 10
DEFAULT
OFF
0.00 sec
OFF
0.00 sec
DEFAULT
OFF
0.00 sec
OFF
0.00 sec
DEFAULT
OFF
50.00Hz
0.00 sec
NONE
OFF
50.00Hz
0.00 sec
NONE
OFF
50.00Hz
0.00 sec
NONE
OFF
50.00Hz
0.00 sec
NONE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents