The following two menus appear if the '2 Systems A/B' option is selected. They replace the Voltage Menu.

3 System A Menu

SETTING
Gn V Element 1 Operation
sets the mode of operation of Voltage Element 1,
whether under or over-voltage
Gn V Element 1 Setting
sets the pickup level of Voltage Element 1
Gn V Element 1 Delay
sets the DTL timer value for Voltage Element 1
Gn V Element 1 Hysteresis
sets the amount of hysteresis required i.e. the
PU/DO ratio
Gn V Element 2 Operation
Gn V Element 2 Setting
Gn V Element 2 Delay
Gn V Element 2 Hysteresis

4 System B Menu

SETTING
Gn V Element 3 Operation
sets the mode of operation of Voltage Element 3,
whether under or over-voltage
Gn V Element 3 Setting
sets the pickup level of Voltage Element 3
Gn V Element 3 Delay
sets the DTL timer value for Voltage Element 3
Gn V Element 3 Hysteresis
sets the amount of hysteresis required i.e. the
PU/DO ratio
Gn V Element 4 Operation
Gn V Element 4 Setting
Gn V Element 4 Delay
Gn V Element 4 Hysteresis
©2011 Siemens Protection Devices Limited
7SG11 Argus 8 Relay Settings
RANGE
OFF, O/V, U/V
5V – 200V step 0.5V
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
1% – 90% step 1%
As per Element 1
As per Element 1
As per Element 1
As per Element 1
RANGE
OFF, O/V, U/V
5V – 200V step 0.5V
0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
1% – 90% step 1%
As per Element 1
As per Element 1
As per Element 1
As per Element 1
Chapter 3 Page 5 of 10
DEFAULT
OFF
80V
0.00 sec
2%
OFF
80V
0.00 sec
2%
DEFAULT
OFF
80V
0.00 sec
2%
OFF
80V
0.00 sec
2%