Installation, connecting up, commissioning
4.1
Important notes on using the device
Safety notices on the use of the device
Note the following safety notices when setting up and operating the device and during all
associated work such as installation, connecting up or replacing the device.
Overvoltage protection
NOTICE
Protection of the external power supply
If power is supplied to the module or station over longer power cables or networks, the
coupling in of strong electromagnetic pulses onto the power supply cables is possible. This
can be caused, for example by lightning strikes or switching of higher loads.
The connector of the external power supply is not protected from strong electromagnetic
pulses. To protect it, an external overvoltage protection module is necessary. The
manufacturers of industrial overvoltage protection devices produce suitable modules.
4.1.1
Notices on use in hazardous areas
EXPLOSION HAZARD
DO NOT OPEN WHEN ENERGIZED.
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
WARNING
WARNING