Installing Wallplate - American Standard ACONT802AS32DA Installation Instructions Manual

Table of Contents

Advertisement

ACONT802AS32DA TOUCH SCREEN AND ACONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Do not install the comfort control where it can be affected
by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall
behind the comfort control.

Installing Wallplate

CAUTION
Electrical Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power before wiring.
The comfort control can be mounted horizontally on the
wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1. Position and level the wallplate (for appearance
only).
2. Use a pencil to mark the mounting holes.
WALL
WIRES THROUGH WALL
AND WIRE SLOT
MOUNTING
HOLES
MOUNTING
SCREWS (2)
Fig. 2. Mounting wallplate.
3. Remove the wallplate from the wall and, if drywall,
drill two 3/16-in. holes in the wall, as marked. For
firmer material such as plaster, drill two 7/32-in.
holes. Gently tap anchors (provided) into the drilled
holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening. See Fig. 2.
5. Insert mounting screws into the holes and tighten.
WIRING (FIG. 5-15)
All wiring must comply with local electrical codes and
ordinances:
1. Select set of terminal identifications (Table 2) that
corresponds with system type (heat/cool or heat
pump in Fig. 3).
2. Loosen the screws for the appropriate system type
selected; see Table 2. Insert wires in the terminal
block under the loosened screw. See Fig. 4.
69-1788—03
WALL ANCHORS (2)
M19916
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to pre-
vent drafts from affecting the comfort control.
Y2
Y2
F
X2
W1
W2
S1
S1
S2
S2
Fig. 3. Selecting terminal identifications for
system type.
Table 2. Selecting Terminal Identifications for
System Type.
System Type
Standard Heat/Cool
Standard Multistage
up to 2 Heat/2 Cool
Heat Pump with
Electric Auxiliary
(Backup) Heat
Heat Pump with
Fossil Fuel Auxiliary
(Dual Fuel) Heat
NOTE: The factory default setting is configured for a
1 Heat/1 Cool System with a gas furnace.
Fig. 4. Inserting wires in terminal block.
IMPORTANT
Use 18 gauge comfort control wire.
2
HEAT PUMP
HEAT/COOL
RC
RC
R
R
W1
O
Y
Y
G
G
B
B
SCREW TERMINALS
M22636
Wallplate
Terminal
Diagram
Identifications
Reference
Heat/Cool
Fig. 5,
Fig. 6
Heat/Cool
Fig. 7,
Fig. 8
Heat Pump
Fig. 9,
Fig. 10,
Fig. 11
Heat Pump
Fig. 12,
Fig. 13,
Fig. 14,
Fig. 15
M19917
Wiring