System Checkout; Installer System Test - American Standard ACONT802AS32DA Installation Instructions Manual

Table of Contents

Advertisement

ACONT802AS32DA TOUCH SCREEN AND ACONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

SYSTEM CHECKOUT

Installer System Test

The Installer System Test mode is used to test the HVAC
system(s). See Table 5. While in System Test mode,
minimum off-time for compressors is bypassed.
The Installer Test is part of the Installer Setup options.
Enter Installer Setup screen and press the Down arrow
key to bring up the test selection(s) quickly.
Installer
Setup
Select
Number
Installer
Test 1
Test Cool
Installer
Test 2
Test Fan
Installer
Test 3
Test Heat
Installer
Test 4
Test Em Ht
Table 5. System Test(s).
Factory Setting
Options
Description
0
Cool is off
0
Fan is off
0
Heat is off
0
Emergency
heat is off
CAUTION
Equipment Damage Hazard.
Minimum compressor off-time is bypassed
during Installer System Test.
Avoid cycling compressor quickly.
Other Choices
Options
Description
1,2
0—cool off
1—cool stage 1 turns on
2—cool stages 1 and 2 on
1
0—fan off
1—fan turns on
1-3
0—heat off
1—stage 1 heat on
2—stages 1 and 2 heat on
3—stages 1, 2 and 3 (Aux
Ht) on
1
0—emergency heat off
1—emergency heat on
2—emergency heat and
auxiliary heat turn on
17
Comments
System selection
determines which
tests are available
and the number of
stages shown.
Available only if
heat pump with
auxiliary heat is
selected.
69-1788—03