STATUS ICONS

The Status Icons are displayed on the Desktop screen and convey operational and diagnostic information. The icons are described in
the table below. Ensure the water heater is properly grounded. Flame sensing requires an adequate earth ground. If the water heater
is not properly grounded it will cause ignition failure.
Icon
Description
Water temperature in the tank has fallen. 'Mercury' increases as tank temperature rises.
Shaded area of the animated thermometer icon will rise and fall in response to water temperature in the storage tank as
sensed from the Upper and Lower Temperature Probes..
Water temperature in the tank has reached the Operating Setpoint.
The control system enters the Standby mode.
The control system is unable to initiate a heating cycle. When 'shutdown', the display will read 'Status: Water Heating
Disabled'.
This will happen whenever a Fault condition is detected by the control system or when the Enable/Disable switch on the
display is in Disable position or Building Management system Enable/Disable circuit is an open circuit. Display will read
"Status: Water Heating Disabled".
The Combustion Blower is being energized.
The Spark Igniter is being energized.
The 24VAC gas valve has been energized.
The control system has sensed flame at the burner from the flame sensor.
See the Sequence of Operation on Page 56.
The control system has declared a Fault condition. The control system must be inspected/serviced by a Qualified Service
Technician. Fault message details can be viewed in the Current Fault menu. Heating operation is disabled (lock out) until
the condition that caused the Fault is corrected. Power to the water heater must be cycled off and on at the breaker to reset
the control system.
NOTE: Cycling power will not reset the control system if the condition that caused the Fault has not been corrected.
The control system has declared an Alert condition. The control system must be inspected/serviced by a Qualified Service
Technician. The water heater will continue to operate during an Alert condition.