MACH® Series Gas-Fired Boiler
Pipe Capacity for Natural Gas
Nominal
Iron Pipe
Internal
Size
Diameter
(Inches)
(Inches)
1/2
0.622
3/4
0.824
1
1.049
1- 1/4
1.380
1- 1/2
1.610
2
2.067
2- 1/2
2.469
3
3.068
4
4.026

3.7.1 Gas Supply Piping by Installer

The boiler and all gas piping connections should be
pressure-tested and must be checked for leaks before
being placed into service. Test with compressed air or
inert gas if possible.
The boiler must be disconnected at the boiler manual
shut-off valve (located at the end of the supplied gas
train) from the gas supply piping system during any
pressure testing of the system at pressures in excess of
1/2 psig (14" W.C.).
During any pressure testing of the gas supply piping
system at pressures equal to or less than 1/2 psig (14"
W.C.), the boiler should be isolated from the gas
supply piping system by closing the manual shut-off.
Some leak test solutions, including soap and water,
may cause corrosion. These solutions should be
rinsed-off with water after testing.
Equivalent Pipe Length
90º Ell
Tee
(Feet)
(Feet)
1.55
3.1
2.06
4.12
2.62
5.24
3.45
6.9
4.02
8.04
5.17
10.3
6.16
12.3
7.67
15.3
10.1
20.2
Maximum Capacity in Cubic Feet of Natural Gas per Hour
Pressure Drop of 0.5 inch Water Column/Equivalent Length of Pipe
20
40
60
120
82
66
250
170
138
465
320
260
950
660
530
1460
990
810
2750
1900
1520
4350
3000
2400
7700
5300
4300
15800
10900
8800
3.8 B
OILER

3.8.1 Piping Design

Water Flow in System
For proper water flow requirements see below.
Incorrect flow may result in eventual damage or
premature failure of the equipment.
Model
1050
900
750
450
300
Contact factory for minimum flow at other than
maximum firing rate.
Page 14
(in feet)
80
100
57
50
118
103
220
195
460
400
690
620
1300
1150
2050
1850
3700
3250
7500
6700
W
P
ATER
IPING
Max Flow
Min Flow
GPM
GPM
105
52
90
45
75
37
45
22
30
15
Installation
150
200
40
35
84
72
160
135
325
280
500
430
950
800
1500
1280
2650
2280
5500
4600
DP ft. at
max flow
12
12
12
8.5
8.5