Rooftop Installations; Minimum Clearance For Boiler Connections - Patterson-Kelley DVSCM-02 Owner's Manual

Patterson-kelley supplement to the standard installation and owner's manual thermific direct vent/sealed combustion gas-fired boiler dvscm-02
Table of Contents

Advertisement

®
Thermific
Gas-Fired Boiler
If the air inlet and/or exhaust vent terminal are through
the sidewall, clearances from other exhaust/inlet,
windows, doors, building openings, snow line, etc
must be as shown in the figure above.
There must be either 5' vertical separation or 10'
horizontal separation between the flue gas outlet and
the combustion air inlet.
The bottom of the flue gas outlet must be located at
least 12 inches above finish grade or snow line, but
must be at least 7 feet above finish grade when located
adjacent to a public walkway. It must also have a
minimum clearance of 4 feet horizontally from, and in
no case above or below, (unless a 4 foot horizontal
distance is maintained,) electric meters, gas meters,
regulators and relief equipment.

3.4.2 Rooftop Installations

10' min.
Combustion
Air Inlet
4' min.
above
snow line
Vent
Combustion
Air Inlet
Flue Gas
Outlet
4' min.
10' min.
4' min.
4' min.
above
snow line
Clearances which must be maintained when both inlet
and exhaust are through the roof are shown in the
figures above.
3.4.3 Minimum Clearance for Boiler
Connections
There are special considerations needed when
installing the air inlet and exhaust duct systems
because of the orientation of these connections on the
boilers.
3.4.3.1 Series 700, 1000, 1200
Round
Damper
90 Elbow
* Dimension shown above is based on 12" round
ductwork.
A minimum clearance of 26 inches is required on the
left side of the boiler to permit the connection of the
air inlet duct to the boiler.
Flue Gas
Outlet
Page 8
Air Inlet
o
*
26" Min.
Installation

Advertisement

Table of Contents
loading

Table of Contents