Siemens FDOOT221 Technical Manual page 117

Automatic fire detectors
Hide thumbs Also See for FDOOT221:
Table of Contents

Advertisement

External alarm indicators
Use as
Parameter
Parameter set name Maximum
set no.
Neural fire
2
Robust
detector
4
Balanced
(FDOOT)
5
Suppression
6
Fast Response
7
High Compensation
0 (ES 13) High Compensation
0 (ES <13) Insensitive
8
High Suppression
9
High Sensitive Fast
Wide-
0
Universal
spectrum
1
Universal
smoke
2
Robust
detector
(FDO)
3
Sensitive
Heat detector
0...4
All parameter sets
(FDT)
Building Technologies
Fire Safety
Number of external alarm indicators that can
be connected:
Voltage
Current
Length of line
Flashing interval times:
Collective maximum current connection factor / Alarm verification
(FDOOT241-9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
current
connection
factor for
ES <30
2
2
2
1.5
2
2
2
For CS1115, the maximum current connection factor values in the column
1
apply for ES <30.
Different load factors due to the different measuring cycles
2
Technical data FDOOT221, FDOOT241-x / -Ax
2 external alarm indicators
–OR-
1 external sounder base and
1 FDSB292
Typ. DC 6...17 V
9...15 mA
Max. 30 m with unshielded
cables, or when the shielding is
connected to the positive pole
of the detector base
Max. 5 m, if the shielding is
connected to earth
Depending on the control panel
Maximum
Alarm verification
current
on control panel
connection
permitted with
factor for
detector ES <13
ES 30
(verification time at
1
the control panel
50 s)
1.5
No
1.5
Yes
1.5
No
2
1.25
2
No
1.5
1.5
1.5
No
1.5
Yes
1.5
No
Specifications
8
Alarm verification on control
panel permitted with detector
ES 13 (verification time at the
control panel 30 s)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
117
007004_n_en_--
01.07.2012