Step 3 — Make Refrigerant Piping

Connections

CAUTION
Do NOT bury refrigerant piping underground. Failure to
comply could result in equipment damage.
The units have large suction lines to minimize friction loss-
es. The units also have the ability to operate at low capacity.
Because of these capabilities, use special care with suction pip-
ing and suction risers to ensure proper compressor oil return
under all operating conditions. If the evaporator is above the
condensing unit, the maximum allowable vertical separation
between the condensing unit and the evaporator is 75 ft
(22.9 m) for all units. Size suction lines in accordance with
Table 6 and Fig. 13.
LEGEND
A
— Pipe A, Suction Riser, without Trap
B
— Pipe B, Suction Riser with Trap
C
— Suction Line to Condensing Unit
D
— Pipe D, Suction Riser Short Lift
RED. — Reducer
STR — Street
NOTES:
1. Short riser, pipe D, is used when routing suction line to
condensing unit connection. See table at right.
2. See Table 6 for values of A, B, and C.
Fig. 13 — Double Suction Riser Construction
18
SIZE REFRIGERANT LINES — Consider the length of pip-
ing required between the condensing unit and indoor unit
(evaporator), the amount of liquid lift, and compressor oil re-
turn. Suction and liquid lines should be sized in accordance
with Table 6. Double suction risers may be required if con-
densing unit is located above the evaporator to assure proper
oil return at minimum load operating conditions. See Table 6
and Fig. 13. Note the indoor unit installation instructions for
additional information.
CAUTION
The field-supplied liquid line solenoid valve must be
installed at the evaporator to avoid possible compressor
damage during unit operation if the maximum allowable
evaporator size is exceeded per Tables 7A and 7B. See
Fig. 14 (for 38APD025-130 dual-circuit units), or Fig. 15
(for 38APS025-065 single-circuit units).
D PIPE DIAMETER
38AP
Dual Circuit
UNIT
Circuit A
Circuit B
SIZE
in.
mm
in.
025
1
/
29
1
/
1
1
8
8
027
1
/
29
1
/
1
1
8
8
030
1
1
/
29
1
1
/
8
8
040
1
3
/
35
1
1
/
8
8
050
1
/
35
1
/
3
3
8
8
060
1
3
/
35
1
5
/
8
8
065
070
1
/
41
1
/
5
5
8
8
080
1
5
/
41
1
5
/
8
8
090
1
5
/
41
1
5
/
8
8
100
1
/
41
1
/
5
5
8
8
115
1
5
/
41
2
5
/
8
8
130
1
5
/
41
2
5
/
8
8
a38-7132
Single Circuit
mm
in.
mm
29
1
/
35
3
8
29
1
/
35
3
8
29
1
3
/
35
8
29
1
5
/
41
8
35
1
/
41
5
8
41
2
1
/
54
8
41
41
41
41
67
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38apd025-130

Table of Contents