9. Adjustment of Water Regulating Valve (Water-Cooled Model Only)

The water regulating valve (also called "water regulator") is factory-adjusted. No adjust-
ment is required under normal use. Adjust the water regulator, if necessary, using the
following procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a
thermometer to check for the condenser drain temperature.
2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure
gauge shows 270 PSIG or the thermometer reads 104-115°F, 5 minutes after a
freeze cycle or icemaking process starts. When the pressure exceeds 270 PSIG, or
the condenser drain temperature exceeds 115° F, rotate the adjustment screw coun-
terclockwise. See Fig. 1.
3) Check that the pressure or the condenser drain temperature holds a stable setting.