Chapter3 Specifications; General Specifications - Mitsubishi Electric MELSEC Q Series User Manual

Safety programmable controller
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
CHAPTER3
3.1

General Specifications

Table 3.1 shows the general specifications of the safety relay module.
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
JIS B 3502, IEC
Vibration
resistance
compliant
Shock resistance
Operating
ambience
Operating
*4
altitude
Installation location
Overvoltage
*1
category
*2
Pollution degree
Equipment
category
3
- 1
3.1 General Specifications
SPECIFICATIONS
Table 3.1 General specifications
Under
intermittent
vibration
61131-2
Under
continuous
vibration
JIS B 3502, IEC 61131-2 compliant (147m/s
Inside of control panel of IP standard 54 or more
* 1: This indicates the section of power supply to which the equipment is assumed to be connected
between the public electrical power distribution network and the machinery within the premises.
Category III applies to devices in fixed equipment such as switching device and industrial machine.
The surge voltage withstand level of equipment for up to the rated voltage of 300V is 4000V.
* 2: This index indicates the degree to which conductive material is generated in the environment
where the equipment is used.
Pollution degree 2 is when non-conductive pollution occurs. However, temporary conductivity may
be produced due to condensation.
* 3: The storage ambient temperature is -20 to 75
modules or extension safety relay modules.
* 4: Do not use or store the programmable controller under pressure higher than the atmospheric
pressure of altitude 0m.
Doing so may cause a malfunction.
When using the programmable controller under pressure, please contact your local Mitsubishi
office.
Specifications
0 to 55
*3
-25 to 75
30 to 85%RH, non-condensing
30 to 85%RH, non-condensing
Frequency
Acceleration
10 to 57Hz
-
57 to 150Hz
9.8m/s
10 to 57Hz
-
57 to 150Hz
4.9m/s
2
, 3 times each in X, Y, Z directions)
No corrosive gases
2000m (6562ft.) or less
III or less
2 or less
Class I
if the system includes any CC-Link safety relay
Amplitude
Sweep count
0.075mm
10 times each in
(0.003inch)
2
-
0.035mm
(0.001inch)
2
-
X, Y, Z
directions
-