Troubleshooting Chart - Goodman PC Installation Instructions Manual

“m” series
Table of Contents

Advertisement

SYMPTOM
High head - low suction
High head - high or normal suction
Low head - high suction
Unit will not run
Condenser fan runs,
compressor doesn't
Low suction - cool compressor
Iced evaporator coil
Compressor short cycles
Registers sweat
High suction pressure
Insufficient cooling

TROUBLESHOOTING CHART

HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
POSSIBLE CAUSE
a. Restriction in liquid line or
TXV not functioning
a. In Cooling: D irty condenser coil
In Heating: Dirty filter, Dirty indoor coil
b. Overcharged
c. In Cooling: C ondenser fan not running
c. In Heating: Indoor blower not running
a. Incorrect TXV.
b. Defective compressor valves
c. TXV not functioning properly
d. Incorrect TXV setting
a. Power off or loose electrical connection
b. Thermostat out of calibration set too high
c. Defective contactor
d. Blown fuses or tripped breaker
e. Transformer defective
f. High or low pressure control open
(Optional)
g. Compressor overload contacts open
a. Loose connection
b. Compressor stuck, grounded or open
winding open internal overload
c. Low voltage connection
d. Capacitor weak, open, or shorted
a. In Cooling: Low indoor airflow
In Heating: Dirty outdoor coil, defective
defrost thermostat, defective defrost
control board, outdoor fan not running, low
refrigerant charge.
b. Low airflow
c. Low refrigerant charge
d. Operating unit in cooling mode below 65°F
outdoor temperature
a. Defective overload protector
b. Unit cycling on low pressure control
c. High pressure switch cuts out
a.
Low airflow
a. Excessive load
b. Defective compressor
c. Reversing valve not seating properly.
a. Improperly sized unit
b. Improper airflow
c. Incorrect refrigerant charge.
d. Incorrect voltage
a. R emove or replace with proper size TXV.
a. C lean coil
b. C orrect System charge
c. R epair or Replace
a. R eplace with correct TXV
b. R eplace compressor
c. C heck for debris in TXV or deformed TXV.
R emove debris or replace TXV.
d. C heck Super Heat
a. C heck for unit voltage at contactor in unit
b. R eset
c. C heck for 24 volts at contactor coil replace if
contacts are open
d. R eplace fuse or reset breaker
e.
C heck wiring - replace transformer
f. C heck high pressure control or check unit
charge
H igh pressure control opens at 610 psig
Low pressure control opens at 22 psig
g. R eplace compressor
N OTE: Wait at least 2 hours for overload to reset
a. C heck for unit voltage at compressor check &
tighten all connections
b. Wait at least 2 hours for overload to reset If still
open, replace the compressor.
c. At compressor terminals, voltage must be within
10 % of nameplate volts when unit is operating
d. C heck capacitor. If defective, replace.
a.
Increase speed of blower or reduce restriction -
replace air filters
b. C heck - should be approximately 400 C FM per
ton, dirty air filters, all duct outlets open
c. Properly charge unit
d. Install or check low ambient control, should be
open below 65°F outdoor temperature
a. R eplace - check for correct voltage
b. C heck refrigerant charge and / or airflow
c. C heck airflow (indoor & outdoor),
check expansion device
a. Increase speed of blower or reduce restriction
replace air filters
a. R echeck load calculation
b. R eplace
c. R eplace
a. R ecalculate load
b. C heck - should be approximately 400 C FM per ton
c. C harge per procedure attached to unit service
panel
d. At compressor terminals, voltage must be within
10% of nameplate volts when unit is operating
17
REMEDY

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ph15

Table of Contents