Programming Field Settings for UL864 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features
or options must be limited to specific values or not used at all as indicated below.
Program feature or option
✱ 08 TEMPORAL SIREN
PULSE
✱ 13 ALARM SOUNDER (BELL)
TIMEOUT
✱ 17 AC LOSS KEYPAD
SOUNDING
✱ 20 VIP MODULE PHONE
CODE
✱ 22 KEYPAD PANIC
ENABLES (PARTITION
SPECIFIC)
✱ 23 MULTIPLE ALARMS
(PARTITION SPECIFIC)
✱ 26 INTELLIGENT TEST
REPORTING
✱ 27 TEST REPORT INTERVAL
✱ 28 POWERUP IN PREVIOUS
STATE
✱ 37 DOWNLOAD COMMAND
ENABLES
✱ 41 NORMALLY CLOSED OR
EOLR (ZONES 3-8)
✱ 42 DIAL TONE PAUSE
✱ 44 RING DETECTION
COUNT
✱ 56 DYNAMIC SIGNALING
DELAY
✱ 64 - ✱ 76 (PAGER OPTIONS)
✱ 77 AUTO RESTORE
PARTIES
Permitted in
Possible settings
UL864? Y/N
N
0 = disable
1 = enable
Y
Enter 01-15 multiplied by 2 minutes.
00 = no timeout.
N
0 = disable
1 = enable
N
Enter 01 - 09 for the first digit; enter
11 for "*" or 12 for "#" for the second
digit.
N
0 = disable
1 = enable
N
0 = disable
1 = enable
N
0 = disable
1 = enable
Y
Enter 0001-9999 for the test report
interval in hours.
Enter 0000 for test reporting.
Y
0 = disable
1 = enable
N
0 = disable
1 = enable
N
0 = EOLR supervision
1 = N.C. loops
Y
Enter the wait time for dial tone
detection:
0 = 5 seconds; 1 = 11 seconds; 2 = 30
seconds.
N
Enter 00 to disable ring detection.
Enter 01-14 for ring counts of 1-14.
Enter 15 to select Answering Machine
Defeat Mode
Y
Enter 00-15 times 15 seconds.
N
NA
Y
0 = disable
1 = restore troubles only
2 = restore troubles and fire alarms
Relay Voice Descriptors and Custom Word
Substitutes Vocabulary........................................ 39
System Layout Worksheets.................................... 40
Output Devices Worksheets ................................... 47
Scheduling Menu Prompts ..................................... 53
Scheduling Worksheets.......................................... 54
–2–
Settings permitted in UL 864
Not used at this time. Must be set to
"0" (disable)
Must be set to "3" (Minimum of 6
minutes).
Must be set to "1" (enabled).
Not used. Must be set to "00".
Must be set to "000" for partition 1
in fire systems.
Must be set to "1" (enabled).
Must be set to "0" (disable).
Must be set to "0024" (Maximum 24
hours)
Must be set to "1" (enable).
Must be set to "0" for all entries
(disable).
Must be set to "0" (EOLR
Supervision).
Must be set to "0" (5 seconds).
Must be set to "00" (disable).
Must be set to "6" (90 seconds).
Not Used
Must be set to "1" (restore troubles
only).