Function Of Thermistor; Heat Pump Model - Daikin FLKS25BVMB Service Manual

Inverter pair floor / ceiling suspended dual type b-series
Hide thumbs Also See for FLKS25BVMB:
Table of Contents

Advertisement

SiBE05-513A
2.

Function of Thermistor

2.1

Heat Pump Model

A
Outdoor Heat
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
Exchanger
Thermistor
(DCB)
2. The outdoor heat exchanger thermistor is used for detecting disconnection of the discharge
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
B
Discharge
1. The discharge pipe thermistor is used for controlling temperature of the discharge pipe.
Pipe Thermistor
(DOT)
2. The discharge pipe thermistor is used for detecting disconnection of the discharge
C
Indoor Heat
1. The indoor heat exchanger thermistor is used for controlling target discharge temperature.
Exchanger
Thermistor
(DCN)
2. The indoor heat exchanger thermistor is used for preventing freezing.
3. The indoor heat exchanger thermistor is used for anti-icing control.
4. During heating, the indoor heat exchanger thermistor is used for detecting disconnection of
Function and Control
A
Four way valve
B
The system sets a target discharge temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the
target discharge temperature can be obtained.
thermistor when cooling.
When the discharge pipe temperature becomes lower than the outdoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
operation.
If the temperature of discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation halts.
thermistor.
The system sets a target discharge temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the
target discharge temperature can be obtained.
During the cooling operation, if the temperature drops abnormally, the operating frequency
becomes lower, then the operation halts.
During the cooling operation, if the heat exchanger temperature in the room where operation
is halted becomes -1°C, it is assumed as icing.
the discharge pipe thermistor.
When the discharge pipe temperature becomes lower than the indoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
Compressor

Function of Thermistor

C
(R3305)
29