Before Installation
General
1. Figure 1 shows dimensions for TP979A-E Dual Zero
Energy Band Pneumatic Thermostats ("Thermostats").
1
Honeywell
Fig. 1. TP979A-E Approximate Dimensions in Inches
(MiIIimeters).
2. Thermostats mount to a deep wall box or on a surface.
3. Table 1 describes Thermostat action and the component
make
thermostats that
up the various TP979 models.
Table 1. TP979A-E Thermostats.
TP979E2006 1
lDirect
with setup
Honeywell Inc.
Copyright 0 1990
TP979A-E Dual
Zero Energy Band
Thermostats

Installation Instructions

Equipment Required

Installation requires the following:
14004068001 Field Mounting Kit (mounting plate,
manifold, and three-port airhead)
CCT735A (MQT735A) Thermostat Tool
CCT348 Pocket Level
AK3052 Tube (5132 in. O.D., 0.030 in. wall)
or
AK3171 Bundled Tubing (5132 in. O-D., 0.030 in. wall)
For surface mounting:
14004193-001 Wall Mounting Ring, 3-3/4 x 4 x l/2
in. (96 x 102 x 13 mm)
Fasteners appropriate to surface (e.g., molly anchors
for drywall mounting)
For flush mounting:
14001355-001 Deep Wall Box (screws provided),
2-5/8 x l-7/16 x 2-9/16 in. (67 x 37 x 65 mm), with
optional 14001354-001 Deep Wall Box Mounting
Bracket for offsetting Deep WaII Box from stud
or
Standard utility conduit box, 4 x 2-1/8 x l-7/8 in.
(102 x 54 x 48 mm)
Calibration may require the following:
All Rights Reserved
l
Pneumatic
95-6023
II. C.
MLF TAB:
a.
2.

Advertisement

loading

Summary of Contents for Honeywell TP979A-E

  • Page 1: Installation Instructions

    Thermostats Installation Instructions Before Installation Equipment Required General 1. Figure 1 shows dimensions for TP979A-E Dual Zero Installation requires the following: Energy Band Pneumatic Thermostats (“Thermostats”). 14004068001 Field Mounting Kit (mounting plate, manifold, and three-port airhead) CCT735A (MQT735A) Thermostat Tool CCT348 Pocket Level AK3052 Tube (5132 in.
  • Page 2: Installation

    Installation 5. Install backplate on box with screws provided (Fig. 4). 1. If flush mounting, mount Deep WalI Box or standard utility conduit box in wall as required. 2. Pull tubing through wall or box. 3. Attach three-port airhead to tubing (Fig. 2). TUBE TO BRANCH Bl LEFT-HAND THERMAL THREE-PORT...
  • Page 3 6. Engage bottom tab of manifold in slot on backplate and 8. Remove shipping stops from Thermostats. To install push manifold straight onto backplate and airhead (Fig. cover, hook two slots on bottom of cover over tabs on bottom of backplate. Swing cover up and over thermostats (Fig.
  • Page 4 Calibration Calibration Check; General Direct-Acting Thermostats (TP970A, After installation, set the thermostats to the desired setpoints and let the system operate long enough to stabilize. Verify that TP971A, D) the system has stabilized before checking calibration. Use Test Thermometer to measure actual temperature are factory calibrated and should require only a of space.
  • Page 5: Cover Information

    General Procedure (All Thermostats) Dual Temperature Thermostats 1. Use Thermostat Tool to remove thermostat cover. With main air at pressure specified for DAY operation, Assemble Gage and Gage Port Needle. turn DAY calibration screw until Gage reads 0 psi. 2. Insert Gage Port Needle into thermostat gage tap. Turn calibration screw in opposite direction until Gage reads 8 psi (56 kPa) +l psi (k7 kPa).