Honeywell Q682A Installation Instructions Manual

Heating/cooling new construction thermostat/subbase package
Hide thumbs Also See for Q682A:

Advertisement

Q682A Subbase) Heating/Cooling New
Construction Thermostat/Subbase
Package—Installation Instructions
Check thermostat and subbase suitability for the heat-
ing, cooling, or heating/cooling system. Refer to Table 1.
Assemble tools required: flat bladed screwdriver, hand
or power drill with 3/16-in. drill bit, wire cutter/stripper or
sharp knife, bubble level or plumb bob and line.
Type of Heating System
to be Controlled
Electric (Line Voltage)—typical baseboard and
radiant
Gas—Direct Spark Ignition (DSI), Intermittent
Pilot (IP), and Standing Pilot (SP)
Heat Pump
Hot Water Zone
Oil
Vent Damper
Warm Air Zone
a
If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermostat
will not be damaged unless it is used to directly control a line voltage system. A Honeywell R841 or R8239D1015 Isolating
Relay must be added to the thermostat control circuit for proper system operation.
b
Consult manufacturer for installation requirements.
M3375
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mer-
cury in a sealed tube, do not place your old control in the
trash.
Y8196A (T8196A Thermostat/
Preparation
TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.
Recycling Notice
D. F. • Rev. 12-94 • ©Honeywell Inc. 1994 •
Assure power is off to the heating, cooling, or heating/
cooling system at the main fuse panel. Most buildings have
a separate switch box or circuit breaker for disconnecting
power to the heating and cooling (if applicable) equipment.
This thermostat is compatible with virtually all heating,
cooling or heating/cooling systems. Refer to Table 1 for
additional thermostat compatibility information.
Conditions/Compatibility
• The R8239D1015 Isolating Relay or R841 Silent Switching
Center must be installed in the thermostat control circuit.
• Compatible.
• Compatible. Assure correct subbase identity is selected for fan
control and changeover control (O terminal for cool and B
terminal for heat). Jumper Y to W for heat pump compressor
control.
• Honeywell 2-wire valves are compatible.
• Some non-Honeywell 2-wire valves require an R8239D1015
Isolating Relay in the thermostat control circuit.
• Some 3-wire valves require an R8239A1052 Isolating Relay
in the thermostat control circuit.
• Compatible.
• Honeywell damper motors are compatible.
• Some non-Honeywell damper motors require an R8239D1015
Isolating Relay in the thermostat control circuit.
control amperage requirement.
• Most are compatible.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.
1
a
a, b
a
Check
• Form Number 69-0637—2
69-0637—2
M3375
a

Advertisement

loading

Summary of Contents for Honeywell Q682A

  • Page 1 If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermostat will not be damaged unless it is used to directly control a line voltage system. A Honeywell R841 or R8239D1015 Isolating Relay must be added to the thermostat control circuit for proper system operation.
  • Page 2: Installation

    Installation Fig. 1—Unpack thermostat. CAPTIVE MOUNTING WHEN INSTALLING THIS PRODUCT… SCREWS THERMOSTAT 1. Read these instructions carefully. Failure to follow COVER them could cause a hazardous condition. 2. Installer must be a trained experienced service techni- cian. 3. After installation is complete, check out product op- eration as provided in these instructions.
  • Page 3: Control Function

    Outlet Box Mounting (Fig. 4) Fig. 3—Leveling methods for subbase. Use a horizontally mounted outlet box if possible. If a vertical outlet box is used, the subbase must be mounted on a 202689A Cover Plate Assembly (ordered separately). Follow the instructions provided with the cover plate as- SPIRIT LEVEL sembly.
  • Page 4 MOUNT THE THERMOSTAT SET TIMER Note the tabs on the top inside edge of the thermostat Adjust the timer by moving the knob clockwise base. These tabs fit the slots molded into the top of the Do NOT reverse the knob. subbase.
  • Page 5: Heating/Cooling System

    HEATING/COOLING SYSTEM Fig. 10—Temperature control levers. Turn on power to the furnace and cooling system. Place the system switch lever to HEAT and fan switch LOW TEMPERATURE HIGH TEMPERATURE lever to AUTO. (BLUE MARK) (RED MARK) SET LEVER SET LEVER Push both temperature setting levers together at least 5°F (3°C) above room temperature.
  • Page 6 Fig. 11—Typical hookup for Y8196A Package (T8196A Thermostat/Q682A Subbase) in heating/cooling system. TIMER FILTER LIGHT THERMOSTAT FALL FALL HEAT HEAT ANTICIPATOR ANTICIPATOR BATTERIES COOL ANTICIPATOR SYSTEM SUBBASE SWITCH SWITCH SWITCH REVERSING REVERSING VALVE/ VALVE/ HEAT COMPRESSOR COOLING HEATING RELAY RELAY...