Midea MS9A-05CR-QD0 Service Manual page 57

Split wall-mounted type air conditioners indoor/outdoor
Table of Contents

Advertisement

9.2.3 Indoor fan speed has been out of control diagnosis and solution
Shut off the power supply
and turn it on 5 seconds
later. Is it still displaying
the error code?
Yes
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
Yes
Check the wires of fan
motor. Are all the
connections good?
Yes
Check whether the fan
motor is normal through
index 1?
Yes
Check whether the main PCB is
normal through index 2?
No
No
No
Replace the fan
No
motor
No
Replace the
main PCB.
No
The
malfunction is
solved?
Yes
55
The unit operates normally.
Find out the cause and
have it solved. For
example, check
whether the fan is
blocked or the bearing
is broken?
Correct the connections.
If the
malfunction is
still existing,
replace the
main PCB