Fig. 10—Mounting the thermostat on the subbase.
A.
ENGAGE TABS AT TOP OF
THERMOSTAT AND MOUNTING PLATE.
CHECKOUT
After the thermostat is mounted on the subbase, check operation as follows:
Heating
Cooling
69-0889
B.
PRESS LOWER EDGE
OF CASE TO LATCH.
Do not check heating system operation by
jumpering thermostat terminals at the
primary control, such as the gas valve,
zone valve, or oil burner control. This
damages the thermostat.
Move the system switch to HEAT and the
fan switch to AUTO.
Press key until the setting is about 10°F
(6°C) above room temperature. After a
short delay, heating should start and the
fan should run (immediately if fan
operation switch is set in E position).
Press key until setting is about 10°F (6°C)
below room temperature. The heating
equipment should shut off.
To avoid possible compressor damage, do
not operate the cooling system when
outside temperature is below 50°F (10°C).
See compressor manufacturer instructions
for further information.
NOTE: When cooling setting is changed,
thermostat may delay up to five minutes
before turning on the air conditioner to
protect the compressor.
Move the system switch to COOL and the
fan switch to AUTO.
Press key until setting is about 10°F (6°C)
below room temperature. The cooling
equipment and fan should start.
4
NOTE:
FOR T8132C
SWING OPEN
COVER TO
CHECK
OPERATION.

Checkout and Settings

Cool
Off
Auto
Warmer
Cooler
Cool
Auto
Cooler
M7493
Heat
On
Off
Heat
On

Advertisement