Installation; Bottom Return Air Inlet; Side Return Air Inlet - Payne PG8MAA Series G Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage deluxe, induced-combustion 4-way multipoise gas furnace
Hide thumbs Also See for PG8MAA Series G:
Table of Contents

Advertisement

The Standard Method:
1. The space has no less volume than 50 cu/ft. per 1,000
Btuh of the maximum input ratings for all gas appliances
installed in the space and
2. The air infiltration rate is not known to be less than 0.40
air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the
infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The
minimum required volume of the space varies with the number of
ACH and shall be determined per Table 3 or Equations 1 and 2.
Determine the minimum required volume for each appliance in
the space and add the volumes together to get the total minimum
required volume for the space.
Table 3 - - Minimum Space Volumes were determined by using
the following equations from the National Fuel Gas Code ANSI
Z223.1- -2012/NFPA 54- -2012, 9.3.2.2:
1. For other than fan- -assisted appliances, such as a draft
hood- -equipped water heater:
= 21ft
Volume
ACH
Other
2. For fan- -assisted appliances such as this furnace:
= 15ft
Volume
ACH
Fan
If:
I
other = combined input of all other than fan- -assisted
appliances in Btuh/hr
I
fan = combined input of all fan- -assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.) The
following requirements apply to the Standard Method and to the
Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.
2
mm
/kW) of the total input rating of all gas appliances
in the space, but not less than 100 in.
opening shall commence within 12 in. (300 mm) of
the ceiling and the second opening shall commence
within 12 in. (300 mm) of the floor. The minimum
dimension of air openings shall be at least 3 in. (80
mm). (See Fig. 8.)
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be
considered as communicating spaces if connected by
one or more permanent openings in doors or floors
having free area of at least 2 in.
2
mm
/kW) of total input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that
freely communicates with the outdoors provided there are
adequate permanent ventilation openings directly to out-
doors having free area of at least 1- -in.
input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, in-
filtration should be adequate to provide air for combus-
tion, permanent ventilation and dilution of flue gases.
I
3
other
1000 Btu/hr
A04002
I
3
fan
1000 Btu/hr
A04003
2
/1,000 Btuh (2,000
2
(0.06 m2). One
2
/1,000 Btuh (4,400
2
/4,000 Btuh of total
However, in buildings with unusually tight construction,
additional air MUST be provided using the methods de-
scribed in the Outdoor Combustion Air Method section.
Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a con-
tinuous, sealed vapor barrier. Openings are gasketed or
sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between wall- -ceiling joints, between
wall panels, at penetrations for plumbing, electrical
and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combus-
tion Air Method below and,
2. Outdoor openings shall be located as required in the Out-
door Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air
Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above
multiplied by reduction Factor in b. above. The min-
imum dimension of air openings shall be not less than
3 in. (80 mm).

INSTALLATION

UPFLOW INSTALLATION

Bottom Return Air Inlet

These furnaces are shipped with bottom closure panel installed in
bottom return- -air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom
filler panel. (See Fig. 9.)
Bottom
Closure Panel
Bottom Filler Panel
Fig. 9 --- Removing Bottom Closure Panel
2. Rotate bottom filler panel downward to release holding
tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.

Side Return Air Inlet

These furnaces are shipped with bottom closure panel installed in
bottom return- -air opening. This panel MUST be in place when
only side return air is used.
10
A10273