Component Locations; Sequence Of Operation; Control Sequence - Greenheck DGX Installation, Operation And Maintenance Manual

92% efficient burners
Table of Contents

Advertisement

Make-Up Air Units showing
Make-Up Air Units showing

Component Locations

Component Locations
Evaporator Coil
Evaporator Coil
Direct Gas-Fired Burner
Direct Gas-Fired Burner
Outdoor
Outdoor
Air Intake
Air Intake
Unit Control Center
Unit Control Center
Model DGX Make-Up Air Unit
Model DGX Make-Up Air Unit
Model DGX Make-Up Air Unit
Outdoor
Outdoor
Air Intake
Air Intake
Evaporator Coil
Evaporator Coil
Model IGX Make-Up Air Unit
Model IGX Make-Up Air Unit
Model IGX Make-Up Air Unit
Outdoor
Outdoor
Air Intake
Air Intake
Evaporator Coil
Evaporator Coil
Model MSX Make-Up Air Unit
with Electric Heat
10
Packaged DX Module for Make-Up Air Unit
Indirect Gas-Fired
Indirect Gas-Fired
Furnace
Furnace
Unit Control Center
Unit Control Center
Unit Control
Unit Control
Center
Center
Model MSX with Electric Heat
Model MSX with Electric Heat

Sequence of Operation

Sequence of Operation
The compressors are energized by an outdoor air
The compressors are energized by an outdoor air
thermostat TS5, located in the unit control center. The
thermostat TS5, located in the unit control center. The
thermostat sensor is located in the intake airstream
thermostat sensor is located in the intake airstream
upstream of the DX coil. The thermostat can be a
upstream of the DX coil. The thermostat can be a
single or dual stage thermostat depending on the
single or dual stage thermostat depending on the
number of compressors. The first stage of cooling
number of compressors. The first stage of cooling
will energize when the outdoor air temperature rises
will energize when the outdoor air temperature rises
above the thermostat set point plus the differential.
above the thermostat set point plus the differential.
The thermostat is factory set at 80°F with a differential
The thermostat is factory set at 80°F with a differential
of 5°F but can be field adjusted. The second
of 5°F but can be field adjusted. The second
stage of cooling will energize when the outdoor air
stage of cooling will energize when the outdoor air
temperature rises above the second stage offset plus
temperature rises above the second stage offset plus
the differential. The second stage offset is factory set
the differential. The second stage offset is factory set
at 10°F and the second stage differential is set at 5°F.
at 10°F and the second stage differential is set at 5°F.
See the chart below for a graphical representation of
See the chart below for a graphical representation of
the control operation.
the control operation.
To summarize the
To summarize the
cooling controls,
cooling controls,
the first stage of
the first stage of
cooling will turn
cooling will turn
on at 85°F and the
on at 85°F and the
(+10° F)
(+10° F)
second stage of
second stage of
cooling will turn
cooling will turn
on at 95°F. The
on at 95°F. The
second stage of
second stage of
cooling will turn
cooling will turn
off at 90°F and
off at 90°F and
Setpoint
Setpoint
Temperature
Temperature
the first stage of
the first stage of
(factory set at 80° F)
(factory set at 80° F)
cooling will turn
cooling will turn
off at 80°F.
off at 80°F.

Control Sequence

1. Heating/Cooling switch (S4) is closed between
terminal R and Y1.
2. N.O. contact on fan relay (RF) is energized and
closed.
3. When the outdoor air temperature is above the
set point plus the differential power passes
through N.O. contacts on outdoor air thermostat
(TS5) and energizes the cooling relay (RC1).
4. When the pressure switches LPS (refrigerant
low pressure switch) and HPS (refrigerant
high pressure switch) are in their normal state
relay R10 will energize. Starting the first stage
compressor contactor.
5. When the outdoor air temperature is above the
second stage offset plus the differential power
passes through N.O. contacts on outdoor air
thermostat (TS5) and energizes the cooling relay
(RC2).
6. When the pressure switches LPS and HPS
(refrigerant high pressure switch) are in their
normal state relay R11 will energize, starting the
second stage compressor contactor.
ON
ON
OFF
OFF
ON
ON
(+5° F)
(+5° F)
OFFSET
OFFSET
(factory set
(factory set
at 10° F)
at 10° F)
OFF
OFF
FIRST
FIRST
SECOND
SECOND
STAGE
STAGE
STAGE
STAGE
COOLING
COOLING
COOLING
COOLING
®