Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
01: Compressor
1 side
02: Compressor
P26
P26
2 side
03: Compressor
3 side
01: Compressor
1 side
02: Compressor
P29
P29
2 side
03: Compressor
3 side
P31
Errors Detected by TCC-LINK Central Control Device
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
C05
C06
C12
Differs according to nature
of alarm-causing error
P30
(L20 displayed.)
Location
of
Description
detection
IPDU
G-TR short-circuit
protection error
IPDU
Compressor
position detection
circuit error
Indoor unit
Other indoor error
(group follower
unit error)
Location
of
Description
detection
TCC-LINK
TCC-LINK central
control device
transmission error
TCC-LINK
central control
device reception
error
General-
Blanket alarm
purpose
for general-
device I/F
purpose device
control interface
TCC-LINK
Group control
follower unit error
Duplicated
central control
address
Error detection
System status
condition(s)
All stop
Overcurrent is momentarily
detected during startup of
compressor.
All stop
Position detection is not going
on normally.
Stop of
There is error in other indoor
corresponding
unit in group, resulting in
unit
detection of E07/L07/L03/L08.
Error detection
System status
condition(s)
Continued
Central control device is unable
operation
to transmit signal.
Continued
Central control device is unable
operation
to receive signal.
Continued
Error signal is input to control
operation
interface for general-purpose
devices.
Continued
Error occurs in follower unit
operation
under group control.
([P30] is displayed on central
control remote controller.)
Continued
There is duplication in central
operation
control addresses.
– 152 –
Check items (locations)
• Check connector connection
and wiring on A3-IPDU P.C.
board.
• Check for defect in
compressor (layer shortcircuit).
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check wiring and connector
connection.
• Check for compressor layer
short-circuit.
• Check for defect in A3-IPDU
P.C. board.
• Check indoor P.C. board.
Check items (locations)
• Check for defect in central
control device.
• Check for defect in central
control communication line.
• Check termination resistance
setting.
• Check for defect in central
control device.
• Check for defect in central
control communication line.
• Check termination resistance
setting.
• Check power supply for
devices at other end of central
control communication line.
• Check defect in P.C. boards
of devices at other end of
central control communication
line.
• Check error input.
• Check check code of unit
that has generated alarm.
• Check address settings.