Atlas Copco QAS 14 Instruction Manual page 83

Alternative current generators
Hide thumbs Also See for QAS 14:
Table of Contents

Advertisement

A
B
Coolant Heater
a6
a2
U1
B-
B+
L
N
b0
b6
(0)
b6
b0
QAS
T1
Q1
Wire Size x
2.5mm 2
14
30/5A
20A
6mm 2
20
30/5A
32A
10mm 2
30
60/5A
50A
400V/480V
16mm 2
40
60/5A
63A
QAS
T1
Q1
Wire Size x
10mm 2
14
60/5A
40A
16mm 2
20
60/5A
63A
35mm 2
30
100/5A
100A
240V-60Hz
50mm 2
40
150/5A
125A
H
I
J
K
L
g0
g0
g0
g6
g54
X2
L3
N
63A
L2
L1
R5
b0
b6
(0)
x0
X1
Wire Size y
2.5mm 2
6mm 2
10mm 2
16mm 2
x0
Wire Size y
X1
10mm 2
16mm 2
16mm 2
25mm 2
e0
e0
e0
e6
e54
c0
c0
Q3
Q4
32A
16A
e0
e0
e0
c0
c0
X3
L3
N
32A
L2
L1
C D E
F
G
H
I
J
K
L
x0
x0
x6
y54
L1
L2
L3
N
PE
(0)
to T13.Tx
y54
PE
1
x0
x0
x6
y54
T13
2
L1
L2
L3
N
PE
PE-EDF
See Note 3
(0)
c0
c6
c54
c0
c6
c54
Q5
16A
30mA
c0
c0
c6
X4
L3
N
L
16A
16A
L2
L1
(0)
- 83 -
X3
Outlet socket 32 A (O)
X4
Outlet socket 16 A (O)
X5
Outlet socket 16 A (O)
X9
Terminal strip
(O)
Optional equipment
QAS
X2
X3
X4
X5
Q2
Q3
Q4
14-20
-
32A
16A
16A-1ph
-
(Q1)
16A
30-40
63A
32A
16A
16A-1ph
(Q1)
32A
16A
Notes
Note 1:
The PE-N connection has to be made at the
alternator-side of main Circuit Breaker Q1.
Note 2:
Link N12.1 to N12.2 on gen-sets without Dual Frequency
(= no potentiometer R12).
Note 3:
With "TB EDF", do NOT connect (N) to (PE) at Q1.
T13 is to be mounted on the (PE)-conductor, in
stead of on the PE-N connection in the cubicle.
Legend
Wire size :
Colour code :
2
0 = black
a = 1 mm
2
b = 1.5mm
1 = brown
2
c = 2.5mm
2 = red
2
d = 4 mm
3 = orange
2
4 = yellow
e = 6 mm
2
5 = green
f = 10 mm
2
g = 16 mm
6 = blue
2
h = 25 mm
7 = purple
2
i = 35 mm
8 = grey
2
9 = white
j = 50 mm
2
54 = green/yel.
k = 70 mm
2
l = 95 mm
2
lx = 95 mm EPR-CSP (BS6195-4C)
2
bx = 1.5 mm NSGAFOeU
Q5
16A/30mA
16A/30mA