Check engine mounts
Check crankcase ventilation system
Check condition of cooling fan assembly
Pressure test cooling system
Check engine electrical ground connection
Replace air filter element (2)
Measure alternator insulation resistance
Check glycol level in coolant (4)
Check PH level of engine coolant (4)
Monitor Insulation Resistance of the main alternator
Replace safety cartridge
Check alternator and starter motor
Check electrical system for security of cables and wear
Test thermostats
Test glow plugs
Inspection by Atlas Copco Service technician
Generators in standby application have to be tested on a
regular basis. At least once a month the engine should run
!
for minimum 30 minutes at a high load (50% - 70%) that
the engine reaches its operating temperature.