TABLE 3 - Unit Water Flow Rate - 60HZ
60Hz
Model
Minimum Flow
030
18.5
040
22.9
050
30.2
075
44.9
100
59.1
125
74.7
150
89.5
175
102.6
200
120.0
50Hz
Model
Minimum Flow
050
25.1
075
37.3
100
49.1
125
62.1
150
74.4
175
85.5
200
98.3
© American Standard Inc. 2001
Units: LPM
Rated Flow
Maximum Flow
27.7
38.8
34.3
48.0
45.3
63.4
67.3
94.2
88.7
124.2
112.0
150.0
134.3
150.0
154.0
175.0
180.0
240.0
Units: LPM
Rated Flow
Maximum Flow
37.7
56.6
56.0
84.0
73.7
110.6
93.3
140.0
111.7
150.0
128.3
160.0
149.0
190.0
18
UNIT WATER PRESSURE
DROP
Measure the water pressure rise across the
standard unit (with built-in pump). The
Externally Available Head (E.A.H) should
approximate those indicated by the E.A.H.
curves, with the corresponding flow rates.
For units (without built-in pump) with field-
installed pump outside the unit, water
pressure drop across the unit should
approximate those indicated by the Internal
Pressure Loss (I.P.L.) curves, with the
corresponding flow rates.
For standard unit with built-in pump, refer to
the E.A.H. curve for the system hydraulic
design. For optional unit without a built-in
pump, refer to the I.P.L. curves. (Refer to
Figure 6 for hydraulic characteristics of all
models.)
CGA-SVX01A-EN