Installation - Toshiba RAV-SM406BTP-E Original Instruction

Air conditioner (split type) indoor unit
Hide thumbs Also See for RAV-SM406BTP-E:
Table of Contents

Advertisement

 Installation space
Reserve sufficient space required for installation or service work.
Air discharge
Ceiling
25
25
A
B
100 or
or more
more
Service door (Ceiling opening)
Floor surface
100 or more
Air discharge
Check port
450
B
Service space
(B for maintenance of air filter)
A
SM40, 45, 56 type
750
SM80 type
1050
SM110, 140, 160 type
1450
 Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed
according to the condition of installation.
For setup method, refer to "Filter sign setting" in the Applicable controls of this Manual.
11-EN
Ceiling
Air intake
25
570
Service door (Ceiling opening)
Air intake
Ceiling
25
570
Service door (Ceiling opening)
Air intake
300 or more
B
700
25
Ceiling
500
570
700
Service door (Ceiling opening)
4

Installation

(Unit: mm)
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only.
Do not apply force to the other parts (such as refrigerant pipe, drain pan, foamed parts, or resin parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
50 or more
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
 External dimensions
External dimensions of flange C
▼ Dimension
SM40, 45, 56 type
SM80 type
SM110, 140, 160 type
– 6 –
C
L
Hanging bolt pitch B
22
Main unit dimension A
Hanging bolt pitch 650
50
D
Drain pan / Drain
pump check cover
A
B
700
765
1000
1065
1400
1465
(Unit: mm)
750
50
345
187.5
355
25
415
570
Electrical
control box
C
D
640
750
940
1050
1340
1450
EN
12-EN