CLEARANCES and HEIGHT REQUIREMENTS
IMPORTANT:
1.
If installing unit into an unvented firebox, minimum required clearances listed in the firebox installation manual
must be met.
2.
If installing unit into a vented firebox with a working damper, minimum clearances shown in Figures 5 through
10 must be met.
3.
If installing unit into a vented firebox with a damper that is always open, no minimum clearances are required.
Heat resistant material (minimum requirements) with no wooden mantel or other combustible projection:
To install the gas logs into a fireplace with no wooden mantel, shelf or other combustible projection above the fireplace
opening, measure the heat resistant material height, per Figure 5, then refer to TABLE A.
Heat resistant materials such as slate and marble must be at least 1/2" thick. Sheet metal should not be installed
onto combustible material.
IMPORTANT: If the unit is installed in a vented fireplace and cannot meet these minimum clearances you must operate the
heater with chimney flue damper open. Refer to "INSTALLING VENTED APPLICATIONS" found on page 17.
TABLE A - Heat Resistant Material Requirements with no Mantel or Combustible Projection
12
����
���������
��������
Figure 5 - Measuring Heat Resistant Material
HEAT RESISTANT
MATERIAL
REQUIREMENTS FOR
MEASUREMENT
SAFE INSTALLATION
12" or more
Hood not required.
8" to less than 12"
Extend heat resistent material to 12" or install
hood. See Figure 6.
Less than 8"
Extend heat resistant material to at least 8" and
install hood. See Figure 6. OR, extend heat
resistant material to a height of at least 12".
�������
����
��������
������ ��
��������� ��
�������