Aube Technologies TH150 Series Installation And User Manual
Aube Technologies TH150 Series Installation And User Manual

Aube Technologies TH150 Series Installation And User Manual

Th150 series vav thermostat

Advertisement

Quick Links

1. Introduction
The TH150 Series electronic thermostat is designed for low-voltage
pressure-dependent variable air volume (VAV) applications. It
comes in four different models:
• TH150-1A
• TH150-1A2T
Depending on the model, the TH150 thermostat can have up to
three outputs connected to the following control devices:
actuators
thermal valves (N.O. and N.C.)
solenoid valves
solid-state relays (SSRs)
silicon-controlled rectifiers (SCRs)
mechanical relays
contactors
Accessories
RC840 or RC840T electromechanical relay
RT850 or RT850T solid-state relay
AC146-410 temperature sensor
AC144-03 temperature sensor
2. Installation
2.1 Mounting Instructions
Remove the thermostat from its base by unscrewing the cap-
tive screw and tilting the bottom of the thermostat up. The
screw cannot be completely removed.
Pass the wires through the center hole of the base and secure
the base to the wall or onto an electrical box.
Wire the thermostat. See section 2.2 for terminal designations
and section 3 for typical wiring diagrams.
Reinstall the thermostat onto its base and secure with the cap-
tive screw.
TH150
• TH150-1F
• TH150-1F2T
TH150 Series
Installation and User Guide
Configuration and status display
Cooling mode
Temperature
adjustment
button
Override button
2.2 Terminal Designations
The designations of the terminals vary according to the particular
model of thermostat. Refer to the following table for the description
of each terminal.
TERMINAL
DESCRIPTION
1
24 VAC
Power supply
2
COM
3
AN1
4
COM
Output 1
3
OPEN
4
CLOSED
5
T2/AN2
Output 2 (models TH150-1A2T and TH150-1F2T)
6
T2/COM
7
T3
Output 3 (models TH150-1A2T and TH150-1F2T)
8
T3
9
COM
External sensor input. (For applications requiring
10
SENSOR
an external sensor, see section 4.2.)
9
COM
Mode Changeover input (N.O. contact). See sec-
11
C-Over
tion 5.5.2.
9
COM
Night Setback activation input (N.O. contact).
12
NSB
See section 5.6.
Note: To configure the terminals, see section 4.
VAV Thermostat
Heating mode
Temperature display
Output power display
Models TH150-1A and TH150-1A2T
Models TH150-1F and TH150-1F2T
400-150-000-C
5/9/06
1/6

Advertisement

loading

Summary of Contents for Aube Technologies TH150 Series

  • Page 1 1. Introduction The TH150 Series electronic thermostat is designed for low-voltage pressure-dependent variable air volume (VAV) applications. It comes in four different models: • TH150-1A • TH150-1F • TH150-1A2T • TH150-1F2T Depending on the model, the TH150 thermostat can have up to...
  • Page 2: Typical Applications

    3. Typical Applications FIGURE 1: Damper control with electric reheat and auxiliary baseboard heating. FIGURE 3: Damper control with automatic changeover, elec- tric reheat and central cooling FIGURE 5: Changeover and NSB inputs sharing the same 24-Vac transformer TH150 FIGURE 2: Damper control with electric reheat and auxiliary hot-water heating FIGURE 4: Temperature control of fresh air supply CAUTION...
  • Page 3: Configuration Menus

    8 8°C (16°F) 8 80% 9 9°C (18°F) 9 90% Remove the thermostat from its base and set the SW2 switch to MENU. Reinstall the thermostat. The thermostat is now in configuration mode. The first digit flashes to indicate that the first item of the menu can now be modified.
  • Page 4: Application Types

    4.3 Output 1 Output 1 is used to control a damper. It controls heating when the thermostat is in heat mode or cooling when the thermostat is in cool mode. Set the following configuration parameters: •...
  • Page 5: Dip Switches

    (see section 4.3.1). For example, if the default mode has been set to heat mode, the contact remains opened when the thermostat is in cool mode. When the thermostat is in heat mode, the contact closes when Output 1 reaches a percentage of its capacity, set via the configuration menu.
  • Page 6: Technical Specifications

    TH150 is placed in automatic changeover. 5.5.2 Changeover Input The thermostat is in the default mode when the contact between ter- minals 9 and 11 is open and switches mode when the contact is closed. The default mode is set via the configuration menu .