General Description

OMEGA® OM5 Series Isolated Signal Conditioning Modules are low cost,
high performance, plug-in signal conditioners. Each OM5 module provides
a single channel of isolated analog input or output. Input modules interface
to all types of external sensors. The modules filter, isolate, amplify, and
convert the input signal to a high-level analog voltage output. The output
modules accept a high-level analog voltage signal from a host system, then
buffer, isolate, and amplify before providing a process current or voltage
output to field devices. Over 115 different OM5 modules are available
encompassing a wide selection of isolated analog input and output functions.
Analog inputs include voltage and current in narrow and wide bandwidths,
Thermocouple, RTD, Potentiometer, Strain Gage, Frequency, and 2-Wire
Transmitter. Custom I/O ranges are also available. All modules are CSA
certified and FM approved for safe operation in Class I, Division 2, Groups
A, B, C, and D hazardous environments.
Accessories include: addressable and non-addressable single, dual, eight
and 16 channel backpanels, available with on-board temperature sensors
and cold junction thermocouple compensation; power supplies; mounting
racks; interface cables, and evaluation boards.
OM5 modules offer several advantages when compared with competitive
parts, while maintaining equivalent price:
• 50 times better noise rejection by using a 6-pole filter with 95dB
NMR, versus a three-pole filter with 60dB NMR; • Lower output noise
• True 3-way isolation • CMR of noise spikes measures 20dB better
than competing models.
Key Specifications
• 1500V Isolation
• Accuracy, 0.05%
• CMR, 160dB
• NMR, 95dB
• Transient Protection, ANSI/IEEE C37.90.1-1989
• 1 V/ C Drift
• Output noise as low as 150 Vrms
• 240VAC Protection for field I/O
• Operating temp range, –40 C/+85 C
• CSA CERTIFIED (Class I, Division 2, Groups A, B, C, D)
• FM APPROVED (Class I, Division 2, Groups A, B, C, D)
• EUROPEAN EMC DIRECTIVE COMPLIANT
• CE APPROVAL for low voltage directive not applicable.
Products comply with ENG1010-1 (IEC1010)
Applications
• DESIGNED FOR INDUSTRIAL PLANT ENVIRONMENTS
• PROTECTS USER EQUIPMENT FROM LIGHTNING AND HEAVY
EQUIPMENT POWER-LINE VOLTAGE
• REDUCES ELECTRICAL NOISE IN MEASURED SIGNALS
• CONVENIENT SYSTEM EXPANSION AND REPAIR
SELECTION GUIDE FOR OM5 ISOLATED
SIGNAL CONDITIONING PRODUCTS
ANALOG VOLTAGE INPUT MODULES, NARROW BANDWIDTH (4Hz BW)
MODEL
INPUT RANGE
OUTPUT RANGE*
OM5-IMV-10A-C
10mV
OM5-IMV-50A-C
50mV
OM5-IMV-100A-C 100mV
OM5-IMV-10B-C
10mV
OM5-IMV-50B-C
50mV
OM5-IMV-100B-C 100mV
OM5-IV-1A-C
1V
OM5-IV-5A-C
5V
OM5-IV-10A-C
10V
OM5-IV-1B-C
1V
OM5-IV-5B-C
5V
OM5-IV-10B-C
10V
OM5-IV-20A-C
20V
OM5-IV-20B-C
20V
OM5-IV-40A-C
40V
OM5-IV-40B-C
40V
ANALOG CURRENT INPUT MODULES, 4Hz AND 1kHz BANDWIDTH
MODEL
INPUT RANGE
OM5-II-4/20-C
4 to 20mA
OM5-II-0/20-C
0 to 20mA
TRUE RMS INPUT MODULES
MODEL
INPUT RANGE (rms)
OM5-IAC-100B-C
0 to 100mV
OM5-IAC-1B-C
0 to 1V
OM5-IAC-10B-C
0 to 10V
LINEARIZED 2- OR 3-WIRE RTD INPUT MODULES (0 to +5V OUTPUT*,
4Hz BW)
MODEL
TYPE***
OM5-IP-N100-C
100
Pt
OM5-IP-100-C
100
Pt
OM5-IP-200-C
100
Pt
OM5-IP-600-C
100
Pt
OM5-IC-120-01-C
10
Cu at 0 C
OM5-IC-120-02-C
10
Cu at 25 C 0 C to +120 C (+32 F to +248 F)
OM5-IN-300-C
120
Ni
LINEARIZED 4-WIRE RTD INPUT MODULES (0 to +5V OUTPUT*, 4Hz BW)
MODEL
TYPE***
OM5-IP4-N100-C
100
Pt
OM5-IP4-100-C
100
Pt
OM5-IP4-200-C
100
Pt
OM5-IP4-600-C
100
Pt
OM5-IC4-120-01-C 10
Cu at 0 C
OM5-IC4-120-02-C 10
Cu at 25 C 0 C to +120 C (+32 F to +248 F)
OM5-IN4-300-C
120
Ni
POTENTIOMETER INPUT MODULES (4Hz BW)
MODEL
INPUT RANGE
OM5-PT-100-C
0 to 100
OM5-PT-500-C
0 to 500
OM5-PT-1K-C
0 to 1K
OM5-PT-10K-C
0 to 10K
THERMOCOUPLE INPUT MODULES (0 to +5V OUTPUT*, 4Hz BW)
MODEL
TYPE**
OM5-ITC-J-C
J
OM5-ITC-K-C
K
OM5-ITC-T-C
T
OM5-ITC-E-C
E
OM5-ITC-R-C
R
OM5-ITC-S-C
S
OM5-ITC-B-C
B
OM5-ITC-C1-C
C
OM5-ITC-N1-C
N
STRAIN GAGE INPUT MODULES ( 5V OUTPUT*, 10kHz BW)
MODEL
INPUT
OM5-WBS38-01-C 10mV Full Bridge Input, (3mV/V) 100 to 10k
OM5-WBS-1-C
30mV Full Bridge Input, (3mV/V) 300 to 10K
OM5-WBS38-03-C 10mV Half Bridge Input, (3mV/V) 100 to 10k
OM5-WBS-3-C
30mV Half Bridge Input, (3mV/V) 300 to 10K
OM5-WBS-2-C
20mV Full Bridge Input, (2mV/V) 300 to 10K
OM5-WBS-4-C
33.3mV Full Bridge Input, (10mV/V) 100 to 10K
OM5-WBS-5-C
100mV Full Bridge Input, (10mV/V) 300 to 10K
ANALOG CURRENT OUTPUT MODULES, 400Hz AND 1kHz BANDWIDTH
MODEL
INPUT RANGE
OM5-IVI-B4-C
0 to +5V
OM5-IVI-A4-C
5V
OM5-IVI-B0-C
0 to +5V
OM5-IVI-A0-C
5V
2
5V
5V
5V
0 to +5V
0 to +5V
0 to +5V
5V
5V
5V
0 to +5V
0 to +5V
0 to +5V
5V
0 to +5V
5V
0 to +5V
OUTPUT RANGE*
BW
0 to +5V
4Hz
0 to +5V
4Hz
OUTPUT RANGE (dc)
0 to +5V
0 to +5V
0 to +5V
INPUT RANGE
–100 C to +100 C (–148 F to +212 F)
0 C to +100 C (+32 F to +212 F)
0 C to +200 C (+32 F to +392 F)
0 C to +600 C (+32 F to +1112 F)
0 C to +120 C (+32 F to +248 F)
0 C to +300 C (+32 F to +572 F)
INPUT RANGE
–100 C to +100 C (–148 F to +212 F)
0 C to +100 C (+32 F to +212 F)
0 C to +200 C (+32 F to +392 F)
0 C to +600 C (+32 F to +1112 F)
0 C to +120 C (+32 F to +248 F)
0 C to +300 C (+32 F to +572 F)
OUTPUT RANGE*
0 to +5V
0 to +5V
0 to +5V
0 to +5V
INPUT RANGE
–100 C to +760 C (–148 F to +1400 F)
–100 C to +1350 C (–148 F to +2462 F)
–100 C to +400 C (–148 F to +752 F)
0 C to +900 C (+32 F to +1652 F)
0 C to +1750 C (+32 F to +3182 F)
0 C to +1750 C (+32 F to +3182 F)
0 C to +1800 C (+32 F to +3272 F)
+350 C to +1300 C (+662 F to +2372 F)
-100 C to +1300 C (-148 F to +2372 F)
EXCITATION
3.333V
10.000V
3.333V
10.000V
10.000V
3.333V
10.000V
OUTPUT RANGE
BW
4 to 20mA
400Hz
4 to 20mA
400Hz
0 to 20mA
400Hz
0 to 20mA
400Hz