Buderus Logano plus GB312 Applications Manual page 51

Gas condensing boiler
Table of Contents

Advertisement

GB312 Applications Manual
12.2 Low loss header selection per
manufacturer
CALEFFI
Multiple boiler applications
Combined
Mains pipe size
Flowrate
(gal/min)
up to 247 gpm
4"
up to 300 gpm
5"
up to 484 gpm
6"
up to 792 gpm
8"
up to 1,330 gpm
10"
up to 1,850 gpm
12"
SINUS
Multiple boiler applications
Combined
Mains pipe size
Flowrate
(gal/min)
up to 115 gpm
4"
up to 190 gpm
5"
up to 250 gpm
6"
up to 375 gpm
8"
up to 480 gpm
8"
up to 745 gpm
10"
up to 1,030 gpm
12"
up to 1,320 gpm
14"
Logano plus GB312 applications manual | 04.2008
Caleffi
Caleffi
Hydro-seperator
Hydro-seperator
selection
selection
ASME registered
Non-ASME
NA548102A
548102A
NA548120A
not offered
NA548150A
not offered
NA548250A
not offered
NA548300A
not offered
NA548300A
not offered
Table 23
Sinus
Nominal Size
Hydro-seperator
selection
7-26-250
4" Flanged
7-26-300
5" Flanged
7-26-400
6" Flanged
7-26-450
8" Flanged
7-26-500
8" Flanged
1-51-218
10" Flanged
1-51-220
12" Flanged
1-51-222
14" Flanged
Table 22
Nominal Size
4" Flanged
5" Flanged
6" Flanged
8" Flanged
10" Flanged
12" Flanged
Technical specifi cations are subject to change without prior notice