Commissioning, inspection, maintenance
Further details regarding the individual steps
Inserting turbulators (if appropriate) and closing the clean-
ing doors
Securing the clean-out cover and the combustion chamber
door
16
(cont.)
1. Insert turbulators B (only in the
3rd flue C) as far as they will go.
2. Close the clean-out doors.
3. Tighten the screws on the clean-
out doors A evenly and diagon-
ally.
1. Tighten down both clean-out cov-
ers B so they seal.
2. Close combustion chamber door
A and tighten it down so it seals.