GENERAL DESCRIPTION

This equipment is an electronic device that controls packaged water cooling systems via air and reversible air/water
heat pumps: (EAC/EAR 0251SM to 1804SM).
The thermostat allows the following operations:
- Unit ON/OFF.
- Select system operating mode.
- Set point adjustment.
- Alarm signal relay.
- Display temperature.
- Status of the unit alarms.
- Possibility of remote ON/OFF.
- A remote controller as an option.
The control makes the system regulation as follow:
- Receives the signals of analogue inputs through the inlet and outlet probe temperature values and the refrigerant
piping probe temperature/pression(the probe is placed in the plater/exchanger) two for model Climatic
- Receives digital inputs through the status of low and high pressure switches, flow switch (water flow) status and
from electrical protection of fan and compressor.
According to the values and status of analogue and digital inputs manages: the output signals; compressor, fan
and status of water pump operating, obtaining the regulation of the inlet water temperature to the unit, regulating
the speed of the air fan volume, activating the defrost cycle (heat pump units only); output signals water exchange
heater, water tank heater, and hot gas valve (all these elements are an option) used to protect the unit, and also
activates the alarm codes about, setting pressure switches, flow switch, water flow, and the electrical protection
of fan and compressor (see alarm section).
- A group of parameters let the control be programmed for each application.
The control incorporated in the unit contains the following devices:
Located in the unit.
The keypad provides control of the system.
Located at the electrical box.
Allows the fan speed to be varied with respect to
the condensing temperature (only for Standard and
FP1 units).
Keypad located in the unit
1
2
mode
on off
Climatic ® 200
A remote controller is offered as an option.
To install this optional remote controller proceed as follow:
- Connect exactly as indicated in electrical diagram.
- The wire should not exceed 50 m.
Fan control plate
set
Located in the unit.
Located at the electrical box.
This device controls the operation of the unit, allowing the regulation
of the system.
Keypad located in the unit
1
2
mode
set
on off
3
4
Climatic ® 400
Electrical box at the unit
Terminal block
*
*Connection to be made by customer
2
Control Module
Fan control plate
Remote controller (option)
Three-lead shielded cable
with a cross-section of 1 mm
MAXIMUM LENGTH 50m
®
400.
2
x 1000
1
2