Specifications - Fujitsu ASYG09LTCA Service Manual

Wall mounted type
Table of Contents

Advertisement

SPECIFICATIONS

ELECTRICAL DATA
TYPE
INDOOR UNIT
OUTDOOR UNIT
COOLING CAPACITY
HEATING CAPACITY
POWER SOURCE
FREQUENCY
RUNNING
CURRENT
INPUT
WATTS
E.E.R.
COP
MOISTURE REMOVAL
AIR CIRCULATION
HIGH
MAXIMUM
CURRENT
FAN MOTOR
POWER SOURCE
High speed
INDOOR
Medium speed
UNIT
Low speed
Cooling
Quiet
High speed
INDOOR
Medium speed
UNIT
Low speed
Heating
Quiet
OUTDOOR UNIT Cooling
OUTDOOR UNIT Heating
2011.05.06
Cool & heat inverter
ASYG09LTCA
AOYG09LTC
2.50 kW
3.20 kW
230 V
50 Hz
Cooling
2.6 A
Heating
3.3 A
Cooling
0.505 kW
Heating
0.66 kW
Cooling
4.95 kW/kW
Heating
4.85 kW/kW
1.3 L/h
800 m 3 /h
Cooling
800 m 3 /h
Heating
Cooling
6.5 A
Heating
9.0 A
230 V
1,300 r.p.m.
1,080 r.p.m.
960 r.p.m.
650 r.p.m.
1,300 r.p.m.
1,120 r.p.m.
960 r.p.m.
650 r.p.m.
750 r.p.m.
750 r.p.m.
NOISE LEVEL
High speed
INDOOR
Medium speed
UNIT
Low speed
Cooling
Quiet
High speed
INDOOR
Medium speed
UNIT
Low speed
Heating
Quiet
OUTDOOR UNIT Cooling
OUTDOOR UNIT Heating
COMPRESSOR AND REFRIGERANT
COMPRESSOR TYPE
DISCRIMINATION
WEIGHT (with oil)
PRECHARGED REFRIGERANT
REFRIGERANT TYPE
Pipe length 15 m
FULL CHARGE
ADDITIONAL CHARGE
MAXIMUM PIPING HEIGHT
DIMENSIONS
INDOOR UNIT
OUTDOOR UNIT
WEIGHT
INDOOR UNIT Shipping / Net
OUTDOOR UNIT
Shipping / Net
1
42 dB
36 dB
32 dB
21 dB
42 dB
37 dB
32 dB
21 dB
50 dB
50 dB
Hermetic type,
4 pole, 3 phase,
DC inverter motor,
Rotary
DA89X1C-20FZ2
9.2 kg
1,050 g
R410A
1,050 g
20 m
1,150 g
20 g/m
15m
H x W x D
282 x 870 x 185 mm
H x W x D
540 x 790 x 290 mm
12 kg / 9.5 kg
37 kg / 33 kg

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aoyg09ltc

Table of Contents